High efficiency tubular heat exchanger
Table of Contents

Advertisement

035-19650-001 Rev. C (0404)
TABLE 2: Replacement PSC Motor / Capacitor Information
High Fire Inputs
BTU/H (kW)
60,000 (17.6)
80,000 (23.4)
100,000 (29.3)
120,000 (35.1)
Hot Surface Ignition System
HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.

FURNACE CLEANING SECTION

NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1.
Turn off the electrical power to the unit.
2.
Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3.
Remove the burner door and remove the burner box cover.
4.
Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5.
Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6.
Remove burners from the burner assembly.
7.
Burners may be cleaned by rinsing in hot water.
8.
Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
1.
Turn off the electrical power to the unit.
2.
Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3.
Remove the upper access panel and remove the burner box
cover.
4.
Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5.
Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6.
Remove burners from the burner assembly.
Unitary Products Group
Airflow
Cabinet Size
CFM (m³)
1,200 (33.98)
B
1,600 (45.31)
C
2,000 (56.63)
C
2,000 (56.63)
D
Motor
Motor
Part Number
Horsepower
024-23271-000
1/2
024-26002-000
3/4
024-23288-001
1.0
024-23238-001
1.0
7.
Remove the upper cover plate at the top of the furnace. Remove
the internal baffle.
8.
The upper portion of the heat exchanger is now exposed.
9.
With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes and then vacuum loose the scale and dirt from
each tube.
10. Clean - vacuum all burners.
11. Replace all components in reverse order. Reconnect all wiring.
12. Restore electrical power and gas supply to the furnace.
13. Check furnace operation.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.
Cleaning the Secondary Heat Exchanger
1.
Follow steps 1 - 8 under cleaning the Heat Exchanger.
2.
Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan. The turbulators can then be gently removed from
the secondary heat exchanger.
3.
Using a stiff wire brush, remove the loose scale or soot from each
tube.
4.
Vacuum the secondary heat exchanger.
5.
Finish the cleaning procedure by following steps 11 thru 13 under
cleaning the Heat Exchanger.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:
1.
Check to see that the power to the furnace and the ignition control
module is ON.
2.
The manual shut-off valves in the gas line to the furnace must be
open.
3.
Make sure all wiring connections are secure.
4.
Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system's
response. Then use the troubleshooting section in this manual to
check the system's operation.
Capacitor
Capacitor
Part Number
Rating
024-20045-000
7.5 f
024-20046-000
10.0 f
024-20446-000
15.0 f
024-20446-000
15.0 f
7