Carrier 50KCQ Installation Instructions Manual page 15

Single package rooftop heat pump with puronr (r---410a) refrigerant sizes: 04, 05, 06
Table of Contents

Advertisement

Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Access Panel
Fig. 20 - - Convenience Outlet Location
Installing
Weatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover
cannot be factory-mounted due its depth; it must be
installed
at
unit
installation.
convenience outlet is covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT
ALL
POWER
CONVENIENCE OUTLET. LOCK- - OUT AND TAG- - OUT
ALL POWER.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
1
approximately
/
-in (13 mm) under screw heads are
2
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 21. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
COVER – WHILE-IN-USE
WEATHERPROOF
Fig. 21 - - Weatherproof Cover Installation
Pwd-CO
Transformer
Control Box
C08128
Cover:
A
weatherproof
For
shipment,
TO
UNIT
AND
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Non- - powered type: This type requires the field
installation of a general- - purpose 125- - volt 15- - A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125- - v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit- - powered type: A unit- - mounted transformer is
factory- - installed to stepdown the main power supply
voltage to the unit to 115- - v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit's control
box access panel. See Fig. 20.
The primary leads to the convenience outlet transformer are
not factory- - connected. Selection of primary power source is
a customer- - option. If local codes permit, the transformer
primary leads can be connected at the line- - side terminals on
the unit- - mounted non- - fused disconnect switch; this will
provide service power to the unit when the unit disconnect
switch is open. Other connection methods will result in the
convenience outlet circuit being de- - energized when the unit
the
disconnect switch is open. See Fig. 22.
UNIT
CONNECT
VOLTAGE
AS
208,
240
230
460
480
575
600
Fig. 22 - - Powered Convenience Outlet Wiring
Using unit- - mounted convenience outlets: Units with
unit- - mounted convenience outlet circuits will often require
that two disconnects be opened to de- - energize all power to
the unit. Treat all units as electrically energized until the
convenience
outlet
de- - energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
15
PRIMARY
TRANSFORMER
CONNECTIONS
TERMINALS
L1: RED +YEL
H1 + H3
L2: BLU + GRA
H2 + H4
L1: RED
H1
Splice BLU + YEL
H2 + H3
L2: GRA
H4
L1: RED
H1
L2: GRA
H2
power
is
also
checked
C08283
and