Tips Continued
COMPLAINT
Fan motor does not run.
Does not cool or only cools slightly
Unit does not run
Evaporator coil freezes up
Compressor runs continually & does
not cycle off
41
TROUBLESHOOTING
CAUSE
Inoperative system button
Broken, loose or incorrect wiring
Open capacitor
Fan speed button defective
Inoperative fan motor
Undersized unit
Indoor ambient thermistor open or
shorted
Dirty filter
Dirty or restricted condenser or evapo-
rator coil
Poor air circulation
Fresh air or exhaust air door open
Low capacity - undercharge
Compressor not pumping properly
Fuse blown or circuit tripped
Loose or disconnected wiring control
board or other components
Dirty filter
Restricted airfl ow
Inoperative thermistor
Short of refrigerant
Inoperative fan motor
Partially restricted capillary tube
Excessive heat load
Restriction in line
Thermistor shorted
SOLUTION
Test button & replace user interface if inopera-
tive
Refer to applicable wiring diagram
Test capacitor & replace if inoperative
Replace user interface if inoperative
Test fan motor & replace if inoperative (be sure
internal overload has had time to reset)
Refer to industry standard sizing chart
See diagnostic codes and replace thermistor if
needed.
Clean as recommended in Owner's Manual
Use pressure wash or biodegradable cleaning
agent to clean
Adjust discharge louvers. Use high fan speed
Close doors. Instruct customer on use of this
feature
Check for leak & make repair
Check amperage draw against nameplate. If not
conclusive, make pressure test
Replace fuse, reset breaker. If repeats, check
fuse or breaker size. Check for shorts in unit
wiring & components
Check wiring & connections. Reconnect per
wiring diagram
Clean filter (see Routine Maintenance)
Check for dirty or obstructed coil. Clean coil
(refer to routine Maintenance)
Check Diagnostic Codes. Check Thermstors and
replace as necessary.
De-ice coil & check for leak
Test fan motor & replace if inoperative
De-ice coil. Replace capillary tube
Unit undersized. Test cooling performance &
replace with larger unit if needed. See sizing
chart.
Check for partially iced coil & check tempera-
ture split across coil
Replace thermistor or electronic control board