TABLE 6: UNIT CLEARANCES
*
72"
Top
†
36"
Front
‡
36"
Rear
*.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
†.
The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.
‡.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
**.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
DETAIL A
5 - 1 / 4
1 7 - 1 3 / 1 6
V i e w o f W a l l A c r o s s f r o m
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
6-13/16
LEFT
21-3/16
19-3/16
FIGURE 14 - BOTTOM DUCT OPENINGS (FROM ABOVE)
Johnson Controls Unitary Products
Right
Left
**
Bottom
G a s P i p e I n l e t
B a s e
P a n
C o i l
32-11/16
6-13/16
Return
Air
27-1/2
18
17-3/16
7-1/8
14-23/32
16-3/8
Bottom
18-1/16
Condensate
Drain
19-5/8
DETAIL B
12"
36"
0"
DETAIL C
NOTE: If the unit includes gas heating, locate the unit so
the flue exhaust is at least:
•
Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
•
Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.
•
Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.
.
Supply
Air
24
21
FRONT
Bottom
Power, Control and
Convenience Outlet
Wiring Entries
63-1/2
127878-YIM-C-1208
2 - 3 / 8
3 - 3 / 4
3 - 9 / 1 6
5 - 3 / 8
6-13/16
12-5/16
Bottom
Gas Supply Entry
15