Mitsubishi Electric PCA-RP71HA PCA-RP71HA Service Manual page 22

Hide thumbs Also See for PCA-RP71HA PCA-RP71HA:
Table of Contents

Advertisement

9-5. HOW TO CHECK THE PARTS
PCA-RP71HA
PCA-RP125HA
Parts name
Room temperature
Disconnect the connector then measure the resistance using a tester.
thermistor
(TH1)
(Surrounding temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
Fan motor
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Relay
Protector
connector
White
Orange
Red
Yellow
Blue
Protector
Black
OPEN : 135i5:
CLOSE : 95i15:
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R
=15kΩ ± 3%
0
Fixed number of B=3480kΩ ± 2%
Rt=15exp { 3480(
273+t
0:
15kΩ
10:
9.6kΩ
20:
6.3kΩ
25:
5.4kΩ
30:
4.3kΩ
40:
3.0kΩ
Normal
4.3k"~9.6k"
Open or short
Connector
PCA-RP71HA
White–Black
140.5"
Black–Blue
Blue–Yellow
Yellow–Red
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Condenser/evaporator temperature
thermistor(TH5)
1
1
) }
273
Check points
Abnormal
(Refer to <Thermistor Characteristic graph> for a detail.)
Normal
PCA-RP125HA
75.6"
15.4"
36.7"
28.5"
23.6"
80.4"
47.8"
22
Abnormal
Open or short
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (:)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pca seriesPca-rp125h

Table of Contents