Operation
Boiler Control System
Vitoflex 300-UF control system parameter
Parameters boiler
1 Boiler temperature,
forward(out) flow
2 Boiler temperature, return(in)
flow
3 Residual oxygen, boiler
4 Boiler temperature,
combustion chamber
5 Negative pressure, boiler,
combustion chamber
6 Underfeed auger cycle, maintain
7 Underfeed auger cycle,
emergency operation
8 Boiler output for emergency
operation
Lower reciprocating screw
1 Underfeed pipe temperature
2 Underfeed auger filling time
3 Combustion chamber filling
time
4 Empty running time, metering
container, underfeed auger
5 Underfeed auger starting cycle
after maintain is reached
6 Underfeed auger starting
cycle after ignition
7 Underfeed auger, pellet
operation
Regulator temperature
1 Boiler forward flow
controller, P(proportional)-
factor
2 Boiler forward flow controller,
D(derivative)-factor
3 Boiler forward flow
controller, I(integral)-factor
4 Boiler forward flow
controller, P-factor
5 Boiler forward flow
controller, D-factor
6 Boiler forward flow
controller, I-factor
7 Hysteresis(lagging behind)
preservation (warm start) ON
8 Hysteresis(lagging behind)
preservation (warm start) OFF
58
(continued)
Unit
Min.
Max.
Default Detailed definition
°C
70
110
85.0
°C
65
95
70.0
%
4.0
15.0
8.0
°C
400
999
750
Pa
20
250
100
%
1
30
%
5
100
%
25
100
100
Unit
Min.
Max.
Default Detailed definition
°C
50.0 120.0
70.0
Sec.
50
999
Sec.
50
999
Sec.
1
90
%
1
100
%
1
100
On/
--
--
Off
Off
Unit
Min.
Max.
Default Detailed definition
--
0
99.9
3.0
--
0
99.9
3.0
--
0
99.0
--
0
99.0
5.0
--
0
99.0
3.0
--
0
99.9
°C
4
20
6.0
°C
0
20
2.0
Vitoflex 300-UF Installation & Operating
Set point for supply temperature, system design
temperature
Set point for return temperature
Oxygen setting, 7-9 for pellets, 8-11 for chips
Set point for combustion chamber temperature
sensor
Set point for negative pressure in combustion
chamber
1
Auger speed for maintain mode
30
Auger speed for emergency mode
Boiler output for emergency mode
Set point for in-feed auger temperature to prevent
back-burn
60
In-feed auger fill time
90
Combustion chamber fill time
25
In-feed auger metering bin, delay on time if sensor
is free
10
In-feed auger speed to fill, warm start
5
In-feed auger speed to fill, cold start
On for pellet operation
Factor for supply, only active when boiler supply
flow temperature is being used. Value 1-3
DO NOT CHANGE SETTING
DO NOT CHANGE SETTING
0
DO NOT CHANGE SETTING
Factor for return
DO NOT CHANGE SETTING
DO NOT CHANGE SETTING
0
DO NOT CHANGE SETTING
A call for heat will start the boiler from maintain
mode, DO NOT CHANGE SETTING
Shut off the boiler from maintain mode.
DO NOT CHANGE SETTING