5 Installation

Symbol on the sticker
A
B
4.4

Type designation and serial number

The type designation and serial number can be found on
a plate behind the front flap and on the main identification
plate. The 7th to 16th digits of the serial number form the
article number.
4.5

CE label

The CE label shows that the products comply with the basic
requirements of the applicable directives as stated on the
identification plate.
The declaration of conformity can be viewed at the manufac-
turer's site.
4.6

Benchmark

Vaillant is a licensed member of the Benchmark Scheme.
Benchmark places responsibilities on both manufacturers
and installers. The purpose is to ensure that customers are
provided with the correct equipment for their needs, that it is
installed, commissioned and serviced in accordance with the
manufacturer's instructions by a competent person approved
at the time by the Health and Safety Executive and that it
meets the requirements of the appropriate Building Regu-
lations. The Benchmark Checklist can be used to demon-
strate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation, commission-
ing and servicing work in accordance with the Benchmark
Code of Practice which is available from the Heating and
Hotwater Industry Council who manage and promote the
Scheme.
Benchmark is managed and promoted by the Heating and
Hotwater Industry Council.
12
Meaning
Heating diaphragm expan-
sion tank connection
Connection from the heat
source to the heat pump (hot
brine)
Connection from the heat
pump to the heat source
(cold brine)
Brine heat source
Energy supply company anti-
cycling time
Installation and maintenance instructions flexoTHERM exclusive 0020213394_01
For more information visit www.centralheating.co.uk
5
Installation
5.1

Checking the scope of delivery

1.
Carefully remove the packaging and padding without
damaging the parts of the product.
2.
Check that the scope of delivery is complete.
Quantity
Description
1
Heat pump
1
Installation set comprising
3 x flat seal (yellow/green) for heating
circuit
1 x 3/4" flat seal for the heating expansion
vessel connection
2 x O-ring seals for brine circuit
1
Expansion relief valve for brine circuit, 1/2",
3 bar
1
Enclosed documentation
5.2

Selecting the installation site

Select a dry room that is frost-proof throughout and in
which the maximum installation height is not exceeded
and the ambient temperature is neither above nor below
the permitted range.
Permissible ambient temperature: 7 ... 25 ℃
Permissible relative air humidity: 40 ... 75 %
Ensure that the installation room has the required min-
imum volume.
Heat pump
R 410 A refriger-
ant filling volume
VWF 57/4
1.50 kg
VWF 87/4
2.40 kg
VWF 117/4
2.50 kg
VWF 157/4
3.05 kg
VWF 197/4
3.95 kg
Ensure that the required minimum clearances can be
maintained.
When selecting the installation site, you must take into
consideration that when the heat pump is in operation, it
will transfer vibrations to the floor and the nearby walls.
Ensure that the floor is level and has sufficient load-bear-
ing capacity to bear the weight of the heat pump and a
domestic hot water cylinder.
Ensure that cables can be easily routed (for brine, hot
water and heating).
Minimum installa-
tion room volume
3.41 m³
5.45 m³
5.68 m³
6.93 m³
8.98 m³