Kidde TRUSENSE COMBO User Manual page 12

Combination multi-criteria optical sensor smoke & carbon monoxide alarm with voice
Table of Contents

Advertisement

are to the closest edge
of the alarm.
NFPA 72 states: "Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally
in 6 feet of appliances
shall be located on the high side of the room." NFPA 72 states: "A row of detectors shall be spaced and located
within 3 ft (0.9m) of the peak of the ceiling measured horizontally."
hin 6 feet of appliances
Not within 6 feet of appliances
12
ANYWHERE ALONG
THIS BOLD SURFACE
Locations permitted for smoke
alarms and smoke detectors
on tray-shaped ceilings.
Figure 7-B
Figure 7-C

Advertisement

Table of Contents
loading

This manual is also suitable for:

2070-vdscr

Table of Contents