2. Specification
DVM S2 (460V)
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
TransmissionCable
Wiring
Connections
Power supply intake
Type
4)
Refrigerant
Factory Charging
Sound Pressure
5)
Sound
SoundPower
6)
Net Weight
Shipping Weight
Net Dimensions
External
(WxHxD)
Dimension
Shipping Dimensions (WxHxD)
Operating
Cooling
7)
Temp. Range
Heating
NOTE
• Specification may be subject to change without prior notice.
1) Nominal capacities are based on (Equivalent refrigerant piping : 25ft, Level differences : 0ft);
- Cooling : Indoor temperature 80℉ DB, 67℉ WB / Outdoor temperature 95℉ DB, 75℉ WB
- Heating : Indoor temperature 70℉ DB, 60℉ WB / Outdoor temperature 47℉ DB, 43℉ WB
2) The standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.  Combination ratio of up
to 184% is allowed depending on operation mode, minimum operation ratio and connected indoor unit models.  DVM Pro 2 design software supports
designing over 130% based on system design.  Refer to the "Design Procedure & Combination Ratio" section of this document for details
3) If outdoor unit is located in a higher position than indoor unit, level difference is 361ft or under.
(If the level difference is higher than 164ft, the PDM kit should be installed)
*PDM kit: Pressure Drop Modulation kit
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
6) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi comvination are theoretical values based on sound results of individual installed units.
7) Cooling operation is possible at -15℃(5℉) or higher if satisfied following conditions.
(If the outdoor temperature below -5℃(23℉), wind(snow) protection duct must be installed on the suction side of the heat exchanger and at least 50%capacity of
the connected indoor units must be operated.) However, if the outdoor unit is installed below the indoor unit, cooling operation is possible only at -5℃(23℉) or
higher.
• For more information regarding capacity correction, please refer to capacity tables available at www.SamsungHVAC.com/downloads.
AM288BXVGJH/AA
AM096BXVGJH/AA
AM192BXVGJH/AA
Min.
AWG
Remark
-
-
Both indoor and outdoor unit
-
lbs (kg)
Cooling
dB(A)
Heating
dB(A)
dB(A)
571 x 1 + 833 x 1
lbs (kg)
(259 x 1 + 378 x 1)
lbs (kg)
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
(51 x 66-3/4 x 30-1/8) x 1 +
inch
(73-1/4 x 66-3/4 x 30-1/8) x 1
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
inch
(75-15/16 x 74-5/16 x 32-11/16) x 1
℉ (℃)
℉ (℃)
-22 ~ 75 (-30 ~ 24)
AM312BXVGJH/AA
AM096BXVGJH/AA
AM216BXVGJH/AA
-
18
F1, F2
Both indoor and outdoor unit
R410A
17.6 x 1 + 27.6 x 1
17.6 x 1 + 34.2 x 1
(8.0 x 1 + 12.5 x 1)
(8.0 x 1 + 15.5 x 1)
64.0
66.8
86.0
571 x 1 + 853 x 1
(259 x 1 + 387 x 1)
608 x 1 + 891 x 1
608 x 1 + 911 x 1
(276 x 1 + 404 x 1)
(276 x 1 + 413 x 1)
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
(51 x 66-3/4 x 30-1/8) x 1 +
(73-1/4 x 66-3/4 x 30-1/8) x 1
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
(75-15/16 x 74-5/16 x 32-11/16) x 1
5 ~ 122 (-15 ~ 50)
5 ~ 122 (-15 ~ 50)
-22 ~ 75 (-30 ~ 24)
AM336BXVGJH/AA
AM096BXVGJH/AA
AM240BXVGJH/AA
-
-
18
18
F1, F2
F1, F2
Both indoor and outdoor unit
R410A
R410A
17.6 x 1 + 34.2 x 1
(8.0 x 1 + 15.5 x 1)
64.8
66.5
67.6
68.5
86.0
87.2
571 x 1 + 853 x 1
(259 x 1 + 387 x 1)
608 x 1 + 911 x 1
(276 x 1 + 413 x 1)
(1,295 x 1,695 x 765) x 1 +
(1,860 x 1,695 x 765) x 1
(51 x 66-3/4 x 30-1/8) x 1 +
(73-1/4 x 66-3/4 x 30-1/8) x 1
(1,363 x 1,887 x 829) x 1 +
(1,928 x 1,887 x 829) x 1
(53-11/16 x 74-5/16 x 32-11/16) x 1 +
(75-15/16 x 74-5/16 x 32-11/16) x 1
5 ~ 122 (-15 ~ 50)
-22 ~ 75 (-30 ~ 24)