Fujitsu ARU7RLF Service Instruction page 59

Slim duct / compact cassette compact wall mounted / wall mounted / floor
Hide thumbs Also See for ARU7RLF:
Table of Contents

Advertisement

Trouble shooting 20
OUTDOOR UNIT Error Method:
2-way valve Thermistor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
2-way valve Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature(°F)
Resistance Value (k )
Temperature(°F)
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Check Point 3 :
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
1
WHITE
RED
3
2
2
WHITE
4
3
3
WHITE
YELLOW
5
4
4
CN39
WHITE
6
5
5
WHITE
BLUE
6
6
7
WHITE
7
8
7
WHITE
BLACK
9
8
8
WHITE
BLACK
1
1
1
RED
GRAY
2
2
2
RED
4
3
3
RED
BROWN
5
4
4
CN40
RED
6
5
5
RED
ORANGE
7
6
6
RED
8
7
7
GREEN
RED
9
8
8
RED
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When 2-way valve Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
14°F
23°F
32°F
312
233
176
104°F
122°F
140°F
25.6
17.1
11.6
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR D (For AOU36RLXFZ)
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
41°F
50°F
59°F
134
103
80.3
158°F
176°F
194°F
8.12
5.78
4.19
02-24
68°F
86°F
62.9
39.6
212°F
3.09