CONCENTRIC HORIZONTAL FLUE ASSEMBLY
COMPONENTS INCLUDED
Item No.
AIR INLET TRANSITION Ø150mm ALU
M87039
LV310665
BEND 90° Ø150mm PP
SAMPLING POINT Ø150mm PP
M70326
EXTENSION Ø150mm(1000mm) PP CUT TO LENGTH
LV310694
M76561
HORIZONTAL TERMINAL Ø150/220mm ALU
10.11.1
HORIZONTAL CONCENTRIC ROOM SEALED APPLICATION

HORIZONTAL FLUE TERMINAL INSTALLATION

If using a C13 flue system with separate Horizontal air inlet and Horizontal combustion outlet the air inlet
and combustion outlet must fit inside a square of 1000mm
When the Water Heater is installed as a Type C
1.
Determine the location of the flue terminal, taking into account minimum distances as detailed in Section 10.4.1 And the
relevant British Standards.
2.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The diameter of the hole
should be no more than 10mm greater than the diameter of the air supply pipe of the terminal.
3.
Determine the required length of the terminal and cut as necessary.
When determining the required length for the flue terminal, the outer wall plate or rosette should be flush
to the wall. (see 10.12.1)
Once cut; remove all burrs and sharp edges
4.
Insert the terminal into the drilled hole. The terminal section should be installed level or with a fall to outside (Max. 10mm
per metre) to prevent the ingress of water.
Item No EKWHF004
Twin-pipe system with a concentric terminal
MODELS EKW206CE,EKW236CE
Description
(Horizontal concentric) appliance, the flue system should be installed as follows:
13
Number
Quantity
1
1
2
5
3
1
4
4
5
1
30