Accessory Installation

Louvered Panels
1 . Remove two screws from top panel where louver will
install.
2 . Slide top of louver panel under lip of the top panel and
slide into place.
3 . Attach with four screws provided.
Figure 16: Louver Removal
www.DaikinApplied.com
Optional Service Valve
1 . Remove clamp securing suction line ext. tube (if
applicable).
2 . Remove connector panel "A".
3 . Remove suction line ext. tube by sweating at reducer/
suction line "B" (reducer required on some models and
remains on suction line). Remove excess braze material
from surface.
4 . Slide service valve "C" onto reducer/suction line "B" (DO
NOT braze at this time).
5 . Install connector panel "A".
6 . Install bracket "D".
7 . Braze valve.
19