7.3 System Test and Commissioning

The Control unit installation must be performed after having carefully read the instructions contained in the
installation and commissioning manual.
Once mechanical installation of the control unit has been completed, perform the following operations:
Check the correct detection line wiring through a multi-meter (refer to chapter 7.2).
Check the correct detection line wiring through a multi-meter or a POL-200-TS (refer to chapter Test
Procedure for the analogue system lines in this manual).
Connect the detection lines to the control unit.
If in use, connect the main alarm sounder (Sounder Circuit fitted 47 KΩ EOL) on the terminals (refer to basic
board topography)
Ensure correct size batteries are fitted to enable required standby time in case of mains failure.
Connect the control unit to the 230 V AC mains by means of a 3-pole cable: L, N, PE (the earth cable must be
longer than the L and N ones) on the CN1 terminal block (the earthing connection is compulsory) and must be
fixed to the cabinet by means of a cable fixing device so that it cannot be accidentally stripped off.
The power supply connection must be performed through the following phases
(refer to basic board topography):
Turn off the main switch of the 230 V AC mains which powers the control unit
Disconnect the CN1 terminal block from the control unit
Connect the 230 V AC mains to the CN1 terminal block
Connect the CN1 terminal block to the control unit
Turn on the main switch of the 230 V AC mains
Install and connect the batteries as indicated in this manual
When the control unit is powered check the following conditions on the front panel:
Green LED "POWER OK"
Yellow LED "FAULTS"
Buzzer
By pressing the Buzzer Silencing key, the buzzer is switched off and the "POWER UP" fault indication is displayed.
By Pressing the "RESET" key the request to enter the level 2 password is displayed (default = 22222).
Enter the password and check the following conditions:
Green LED "POWER OK"
Yellow LED "FAULTS"
No faults signalling on the display
28
= on
= flashing
= continuous sound
= on
= off