Carrier 558J Series Service And Maintenance Instructions page 34

Nominal 15 to 27.5 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor's Dirty LED flashing.
S The controller's Trouble LED flashing.
S The controller's supervision relay contacts toggle.
The operation of a sensor's dirty test can be changed so
that the controller's supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing for approximately 60 seconds until
the sensor's Alarm LED turns on and its Dirty LED
flashes twice.
2. Reset the sensor by removing the test magnet and
then holding it against the sensor housing again for
approximately 2 seconds until the sensor's Alarm
LED turns off.
Remote Station Test
The remote station alarm test checks a test/reset station's
ability to initiate and indicate an alarm state.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing the dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify proper authorities if connected to
a fire alarm system.
SD−TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station's Alarm LED turns
on.
3. Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
4. Verify that the test/reset station's Alarm LED turns
off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset
station's ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 41 and configured to operate the controller's
supervision relay. For more information, see "Changing
the Dirty Sensor Test."
Fig. 41 − Remote Test/Reset Station Connections
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an
unnecessary evacuation of the facility.
If the test/reset station's key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an
unnecessary evacuation of the facility.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
Dirty Sensor Test Using an SD−TRK4
1. Turn the key switch to the RESET/TEST position for
two seconds.
2. Verify that the test/reset station's Trouble LED flash-
es.
Detector Cleaning
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
34