Outdoor Unit : CM2472
: KMS0972
Indoor Unit
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY:
INDOOR
ENT. TEMP. °F (°C)
W.B.
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
NOTE
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.
2.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
3
×
25,400 BTU/h
D.B.
65
(18.3)
TC
25,690
72 (22.2)
SHC
20,210
76 (24.4)
SHC
23,130
80 (26.7)
SHC
25,690
84 (28.9)
SHC
25,690
88 (31.1)
SHC
25,690
TC
26,810
72 (22.2)
SHC
16,790
76 (24.4)
SHC
19,700
80 (26.7)
SHC
22,960
84 (28.9)
SHC
25,870
88 (31.1)
SHC
26,810
TC
27,910
72 (22.2)
SHC
13,360
76 (24.4)
SHC
16,270
80 (26.7)
SHC
19,360
84 (28.9)
SHC
22,440
88 (31.1)
SHC
25,360
TC
28,980
72 (22.2)
SHC
9,590
76 (24.4)
SHC
12,670
80 (26.7)
SHC
15,760
84 (28.9)
SHC
18,670
88 (31.1)
SHC
21,590
TC
29,880
76 (24.4)
SHC
9,070
80 (26.7)
SHC
12,160
84 (28.9)
SHC
15,070
88 (31.1)
SHC
18,160
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.
AIR FLOW RATE:
OUTDOOR
AMBIENT TEMP. °F (°C)
75
85
95
(23.9)
(29.4)
(35.0)
24,800
23,840
23,190
19,870
19,360
19,010
22,790
22,270
22,100
24,800
23,840
23,190
24,800
23,840
23,190
24,800
23,840
23,190
25,900
24,910
24,290
16,440
15,930
15,760
19,360
19,010
18,670
22,440
22,100
21,760
25,530
24,910
24,290
25,900
24,910
24,290
26,980
25,970
# 25,400
13,010
12,500
12,330
15,930
15,590
15,240
19,010
18,670
18,330
22,100
21,590
21,410
25,020
24,670
24,330
28,030
26,990
26,500
9,240
8,900
8,730
12,330
11,810
11,640
15,410
15,070
14,730
18,330
17,990
17,810
21,240
20,900
20,730
28,920
27,870
27,460
8,730
8,390
8,210
11,810
11,470
11,300
14,730
14,390
14,390
17,810
17,470
17,300
37
883 CFM
105
115
(40.6)
(46.1)
22,040
17,290
18,500
16,440
21,410
17,290
22,040
17,290
22,040
17,290
22,040
17,290
23,110
17,700
15,240
13,010
18,160
15,930
21,240
17,700
23,110
17,700
23,110
17,700
24,180
18,070
11,810
9,590
14,900
12,500
17,990
15,590
20,900
18,070
23,810
18,070
25,010
18,380
8,210
5,980
11,130
8,900
14,210
11,990
17,300
15,070
20,210
17,990
25,330
18,590
7,530
5,470
10,610
8,560
13,700
11,640
16,610
14,560

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cm31721972cm

Table of Contents