Cleaning The Siphon And Heat Exchanger; Checking The Burner; Checking The Non-Return Valve In The Air-Gas; Manifold - Worcester GR8300iW 30 S Installation And Maintenance Instructions Manual

Gas fired condensing system boiler
Table of Contents

Advertisement

8.9

Cleaning the siphon and heat exchanger

WARNING:
Gaskets and seals - gas related components
▶ Replace gaskets and seals when disturbing gas related components
(e.g. burner, electrode assembly etc.), after cleaning the heat
exchanger.
▶ Do not attempt the cleaning procedure unless new gaskets and seals
are available.
There is an optional tool available to assist in cleaning the heat
exchanger, part number 7 719 001 996.
8.9.1

Checking the burner

1. Remove the combustion cover  Fig. 61.
2. Unscrew the screws on the burner cover.
3. Remove the burner cover.
1.
Fig. 75 Removing the burner cover
Greenstar 8000 Life – 6720883858 (2019/02)
▶ Remove the burner and clean its components.
1.
Fig. 76 Burner
▶ Reinstall the burner in reverse order, including a new gasket.
2.
▶ Install the burner and the burner cover.
▶ Check the gas/air ratio.
8.9.2
1. Unscrew the screws at the air-gas manifold.
2. Remove the air-gas manifold.
0010023602-001
1.
Fig. 77 Removing the air-gas manifold
Checking the non-return valve in the air-gas manifold
1.
2.
Inspection and maintenance
0010023603-001
0010017096-001
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenstar 8000 lifeGr8300iw 35 s

Table of Contents