Certification
Section 6.1.7

Other Approvals

This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1500 has passed the following Electromagnetic Compatibility (EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
42
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Enclosure Ports
Installation Guide
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
Other Approvals
RUGGEDCOM RX1500
Severity
Levels
4
a
Note
4
4
3
4
3
a
Note