SYSTEM START-UP
At initial start up, with the Economy Feature active, the control
establishes a 145°F target temperature. To test the high limit
shut-off function, the Economy Dial must be turned to OFF.
Once tested, restore the Economy setting. If the heating
demand is high, the target will increase over time to satisfy the
heat load.
NOTE:
Smart DHW Priority : During a call from indirect water heater, the control will de-energize the circulator contacts (C1/C2) to heat
only the indirect tank ensuring an adequate supply of domestic hot water. The control will re-energize the circuator when the
indirect tank is satisfied or if the boiler temperature reaches 170˚F. If the indirect call continues for 45 minutes, the control will
overide the priority function energizing the circulator to provide space heating.
LED LEGEND and TEST/SETTINGS BUTTON
u
TEMP ACTIVE Indicates that the
Fuel Smart HydroStat control is pow-
ered and that the temperature function
is active.
v
TEMP HIGH TEMP Illuminates
when the boiler water temperature
reaches the high limit setting. It will
remain lit until the water temperature
falls 10°. The Fuel Smart HydroStat pre-
vents burner operation while this LED is on.
w
LWCO ACTIVE Indicates that the low water cut-off (LWCO)
function of the Fuel Smart HydroStat is active. When the
control is installed with a Hydrolevel Electro-Well, this LED will be
on at all times when the control is powered.
IMPORTANT: If the control is installed with a well other than the
Electro-Well, this LED will not illuminate indicating that the control
is not providing low water cut-off functionality.
LWCO LOW WATER Illuminates if the boiler is in a low water
condition. The Fuel Smart HydroStat will prevent burner operation
during this condition. IMPORTANT: The system must be checked
by a qualified heating professional prior to resuming operation.
WARNING: DO NOT ADD WATER UNTIL THE BOILER
HAS FULLY COOLED.
ECONOMY ACTIVE Indicates that the Thermal Targeting
function is active and the Fuel Smart HydroStat will reduce boiler
temperature to conserve fuel. The Economy feature is activated
using the ECONOMY dial.
ECONOMY TARGET When the Economy feature is active,
the Fuel Smart HydroStat continually sets target temperatures
HOW THERMAL TARGETING WORKS
Thermal Targeting technology analyzes thermostat activity and
continually evaluate how much heat the house requires. When
it is very cold outside, the heat demand is high and the Fuel
Smart HydroStat will raise the boilerʼs Target temperature to
provide needed heat to the home. When the outside tempera-
ture is milder, the heat demand is lower. During these periods,
the Fuel Smart HydroStat will lower the boilerʼs Target temper-
ature – saving fuel – while continuing to provide comfort to the
house.
❶ ❷ ❸ ❹ ❺ ❻ ❼
TEMP LWCO ECONOMY
TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold the Test/Settings
button for 5 seconds. The display will read LCO.
The red Low Water light should illuminate and the burner circuit
(B1 and B2) should de-energize. NOTE: The control must be
installed with a Hydrolevel Electro-Well for low water cut-off func-
tionality.
To View Current Settings: Press and release the Test/Settings Button
in short intervals to sequentially display the following settings:
below the high limit setting to maximize
fuel efficiency. When the boiler water
reaches the target temperature, the LED
illuminates and the burner will shut
down. The boiler water will continue to
circulate and heat the house as long as
the thermostat call continues. The LED
will stay lit until the boiler temperature
drops to the differential set point (see
Target Temp Differential on page 4) at
which point the boiler will be allowed to
fire again. NOTE: This LED illuminates
regularly during normal boiler operation.
LWCO TEST LCO
HIGH LIMIT SETTING HL
q
LOW LIMIT SETTING LL
q
ECONOMY SETTING ECO
q
CURRENT TARGET TEMPERATURE
q
PRE-PURGE SETTING Pur
The display will return to boiler temperature (default) if
Test/Settings Button is not pressed for 5 seconds.
15
ooo