OPA2-2T(H)-VC
Operation terminal for TCX2
Features
Remote access to controller state, setpoints, inputs and outputs
Access to time schedule and clock settings
Access to configuration parameters
RS485 peer to peer communication according to proprietary
protocol of Vector Controls GmbH
The terminal adapts itself to the TCX2 controller used. One terminal
thus fits all the configuration variations of the TCX2 product range.
Internal temperature sensor
Internal humidity sensor (H version) or with AES-HT-A3 for
example
2 passive inputs: (only available with firmware version V1.1 and up)
Applications
Configuration and operation of TCX2 controllers
Remote supervision (RS485)
General Description
The OPA2-2T(H)-VC is a remote display and operation terminal for TCX2 series controllers.
Ordering
Item Name
Item Code
OPA2-2T-VC
40-50-0047
OPA2-2TH-VC
40-50-0023
Mounting location
Install the operation terminal on an easy accessible interior wall, approx. 1.5 m above the floor in an area
of average temperature.
Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.
Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
Location of mounting is less critical if external temperature sensors are used.
Installation
1.
Connect the wires to be connected to the terminals of the power case according to wiring diagram
2.
Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2") off the
surface of the mounting plate.
3.
Ensure that the jumpers are set correctly.
4.
Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting
plate.
5.
Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a
gentle way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt.
This is normal. Do not use excessive force!
6.
With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the
screw too much.
Dimensions [mm] (in)
88 (3.5)
Doc: 70-00-0379, V1.2, 20140213
Subject to alteration
OPA2-2T(H)-VC Operation Terminal
Description/Option
Operation terminal for TCX2-type controller with peer to peer RS485
communication and internal temperature sensor and 2 passive inputs
As above with internal humidity sensor
21
32 (1.2)
(0.8)
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
Technical Data
Page 1

Advertisement

loading

Summary of Contents for Vector OPA2-2T-VC

  • Page 1 Access to configuration parameters  RS485 peer to peer communication according to proprietary protocol of Vector Controls GmbH  The terminal adapts itself to the TCX2 controller used. One terminal thus fits all the configuration variations of the TCX2 product range.
  • Page 2: Technical Specification

    X1, X2 Range Open contact to GND Communication Communication Type RS485, Peer to peer, Protocol VCPP: Vector Controls Proprietary Protocol Cabling Shielded Twisted Pair (STP), CAT5 or CAT6. Impedance balanced 100 to 120 ohm Nominal capacitance 50 pF/m 16pF/ft or lower...
  • Page 3: Display And Operation

    During a pending delay the hand symbol will be shown. For example the condition to activate the controller with 1FU is met, but a startup delay is specified. The controller will remain switched off and show the hand symbol until the delay expired. Doc: 70-00-0379, V1.2, 20140213 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration www.vectorcontrols.com...
  • Page 4: Creating Time Schedules

    Choose operation mode, setpoint or position of output Characteristics of action (e.g. 0–100% for A1) appear (5 bar indicates step 5 complete) Pr01 Press UP/DOWN to select, OPTION to complete Doc: 70-00-0379, V1.2, 20140213 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration www.vectorcontrols.com...
  • Page 5: Error Messages

    Parameter copy mode: Check sum mismatch of eeprom data. Data in external eeprom corrupt. -50°C: Internal temperature measurement is limited to 0°C (32°F). Values lower than 0°C (32°F) will be shown as - 50°C (-58°F) Doc: 70-00-0379, V1.2, 20140213 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration www.vectorcontrols.com...
  • Page 6 Press OPTION to step to alarm 2. Repeatedly press OPTION key to step through all available alarms and select or deselect them by pressing UP or DOWN. Press POWER to leave the alarm selection routine and return to the parameter selection level. Doc: 70-00-0379, V1.2, 20140213 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration www.vectorcontrols.com...
  • Page 7 Fail: Err6, Checksum mismatch. The checksum of the source data was incorrect. Data corruption. This may happen if the plug-in has not been written to before or data corruption took place. Doc: 70-00-0379, V1.2, 20140213 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration...

This manual is also suitable for:

Opa2-2th-vc40-50-004740-50-0023