1. PRODUCT NAME
®
VIKING HORIZON
MIRAGE
Model B-1 Extended Coverage
20' x 20' (6.1 m x 6.1 m)
Concealed Pendent Sprinkler
Standard Orifice Sprinkler
Base Part No. 08498
Manufactured since 1993
Large Orifice Sprinkler
Base Part No. 10485
Manufactured since 1998
Cover Plate Assembly
Base Part No. 09804
Manufactured since 1996
2. MANUFACTURER
THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058 U.S.A.
Telephone:
(616) 945-9501
(800) 968-9501
Fax Number:
(616) 945-9599
From outside U.S.A.:
Telephone:
+1 (616) 945-9501
Fax Number: +1 (616) 945-9599
e-mail:
techsvcs@vikingcorp.com
3. PRODUCT DESCRIPTION
The Viking Extended Coverage Hori-
®
®
zon
Mirage
Concealed Sprinkler is a
small, solder link and lever spray sprin-
kler designed for installation on con-
cealed pipe systems.
Equipped with a special deflector, the
sprinkler is designed to meet light haz-
ard density requirements for specific ex-
tended areas of coverage when the re-
quired minimum water supply is pro-
vided at the sprinkler.
After the sprinkler system has been
tested and the ceiling finish applied, the
sprinkler is hidden from view by a low
profile, small diameter cover plate, in-
stalled flush to the ceiling. The cover
plate is available in several decorative
finishes to meet design requirements.
The "push on", "thread off" design al-
lows for easy installation of the cover
plate, with up to 1/2" (12,7 mm) adjust-
ment. The "thread off" feature is de-
signed to prevent unwanted disengage-
ment of the cover assembly, while allow-
ing it to be removed and reinstalled to
permit temporary removal of ceiling pan-
els without taking the sprinkler system
out of service and removing the sprinkler.
Inside the body of the sprinkler, the de-
flector and sealing assembly are held in
position by a heat sensitive fusible link.
The sprinkler is listed as a standard
response sprinkler when installed ac-
cording to the listed 20 Ft. X 20 Ft. (6.1
M X 6.1 M) spacing. (Refer to the Ap-
proval Chart for other listings available).
Note: Units of measure in parentheses may be approximations.
Form No. F_061593
TECHNICAL DATA
®
Viking Horizon
Extended Coverage Con-
Sprinkler
Temperature
Classification
Ordinary
Maximum Area
of Coverage
Length X Width
16 ft. x 16 ft.
4.9 m x 4.9 m
18 ft. x 18 ft.
5.5 m x 5.5 m
20 ft. x 20 ft.
6.1 m x 6.1 m
Maximum Area Nominal
of Coverage
Length X Width
16 ft. x 16 ft.
4.9 m x 4.9 m
18 ft. x 18 ft.
5.5 m x 5.5 m
20 ft. x 20 ft.
6,1 m x 6,1 m
1
Temperature rating of Viking Horizon
2
Based on NFPA-13. Other limits may apply depending on fire loading, sprinkler location, and other
Authority Having Jurisdiction requirements. Refer to specific installation standards.
3
This chart shows listings and approvals available at time of printing. Other approvals are in process.
Check with manufacturer for additional approvals.
4
For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the next
larger "Area Of Coverage" listed for the sprinkler used. The distance from sprinklers to walls shall not
exceed one half the sprinkler spacing indicated for the "Minimum Water Supply Requirement" used.
5
Metric K Factor shown is for use when pressure is measured in kPa. When pressure is measured in
BAR, multiply the metric K Factor shown by 10.0.
6
Accepted for use by City of New York Department of Buildings. MEA 89-92-Vol IX
7
Lisiting is limited to light hazard occupancies with smooth, flat, Horizontal ceilings.
Mirage
®
®
cealed Sprinkler
Figure A
Nominal
Highest Ambient
Temperature
Temperature Allowed
1
Rating
o
o
165
F (74
C)
Areas of Coverage 3
Standard Orifice
®
®
Horizon
Mirage
Extended Coverage Concealed Sprinklers
Nominal
Minimum
4
K
Water Supply
5
Factor
Requirements
5.5
Listed for this spacing as Quick Response Extended Coverage Sprinkler.
See Quick Response Extended Coverage Sprinkler page 58 a-c.
7,9
Listed for this spacing as Quick Response Extended Coverage Sprinkler.
5.5
See Quick Response Extended Coverage Sprinkler page 58 a-c.
7,9
5.5
40 GPM @ 53.0 PSI
7,9
151.4 L/Min @ 368 kPa
Areas of Coverage
Large Orifice
®
®
Horizon
Mirage
Extended Coverage Concealed Sprinklers
Minimum
4
K
Water Supply
5
Factor
Requirements
Listed for this spacing as Quick Response Extended coverage Sprinkler.
8.0
See Quick Response Extended Coverage Sprinkler page 58 a-c.
11,5
8.0
Listed for this spacing as Quick Response Extended coverage Sprinkler.
See Quick Response Extended Coverage Sprinkler page 58 a-c.
11,5
8.0
40 GPM @ 25.0 PSI
11,5
151.4 L/Min @ 174 kPa
Footnotes
®
Mirage
®
Concealed Sprinkler is stamped on the sprinkler body.
Table 1
Replaces page 87 a-d, dated August 11, 1997.
(Replaced Identification Stripe with Stripe or Dot)
®
HORIZON
MIRAGE
EXTENDED COVERAGE
20 Ft X 20 Ft (6.1 M X 6.1 M)
CONCEALED SPRINKLER
Standard Orifice:
Figure B
Cover Assembly
2
at Ceiling
Temperature Rating
o
o
100
F (38
C)
165
UL
C-UL
Yes
Yes
3
7
7
UL
C-UL
Yes
Yes
Sprinkler 87 a
®
P/N 08498
Large Orifice:
P/N 10485
P/N 09804
Required
o
o
F(74
C)
6
--
NYC
Yes
--
--
--
--
--

Advertisement

loading

Summary of Contents for Viking HORIZON MIRAGE B-1

  • Page 1 Ceiling Temperature Rating e-mail: techsvcs@vikingcorp.com Ordinary F (74 F (38 F(74 3. PRODUCT DESCRIPTION Areas of Coverage 3 The Viking Extended Coverage Hori- Standard Orifice ® ® ® ® Mirage Concealed Sprinkler is a Horizon Mirage Extended Coverage Concealed Sprinklers...
  • Page 2 ® Horizon Mirage Concealed Sprin- Deflector Pins: Stainless Steel UNS- Viking Technical Data may be found on klers are protected with a plastic pro- S30300 The Viking Corporation’s Web site at : tective shell, which should remain in Lever Bar: Copper Alloy UNS-C72500 http://www.vikingcorp.com...
  • Page 3 D. Use care when locating sprinklers 3: Use only the special wrenches 3: From below the ceiling, gently designed for installing Viking Ho- place the base of the cover plate near fixtures that can generate heat. ®...
  • Page 4 For tire system must be inspected for The internal diameter of the spe- ® damage and repaired or replaced as Viking Extended Coverage Horizon ® ® cial Horizon Mirage Concealed ®...