Preparing the Site

Temperature Requirements

The switch requires a operating temperature of 32 to 104° F (0 to 40° C). If the switch is not operating, the
temperature must be between -40 to 158° F (-40 to 70° C).

Humidity Requirements

High humidity can cause moisture to enter the switch. Moisture can cause corrosion of internal components
and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size.
The switch is rated to operate at 8 to 80 percent relative humidity, with a humidity gradation of 10 percent
per hour. For nonoperating conditions, the switch can withstand from 5 to 95 percent relative humidity.
Buildings in which the climate is controlled by air-conditioning in the warmer months and by heat during the
colder months usually maintain an acceptable level of humidity for the switch equipment. However, if the
switch is located in an unusually humid location, you should use a dehumidifier to maintain the humidity
within an acceptable range.
Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide
1

Advertisement

Table of Contents
loading

Summary of Contents for Cisco Nexus 9504

  • Page 1: Table Of Contents

    However, if the switch is located in an unusually humid location, you should use a dehumidifier to maintain the humidity within an acceptable range. Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 2: Altitude Requirements

    • Strong EMI, especially when it is caused by lightning or radio transmitters, can destroy the signal drivers and receivers in the chassis and even create an electrical hazard by conducting power surges through lines into equipment. Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 3: Shock And Vibration Requirements

    To plan for the power requirements of a switch, you must determine each of the following: • Power requirements for all of the switch components • Minimum number of power supplies required to power the components installed in the switch Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 4 420 W 360 W – 32-port 40-Gigabit QSFP+ I/O module (N9K-X9432PQ) 300 W 240 W Fabric Modules (N9K-C9504-FM) 3 to 6 125 W 100 W Fan Trays (N9K-C9504-FAN) 135 W 110 W Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 5 Typically, power receptacles are placed on the rack with the switch. Power Supply Maximum Distance Between Receptacle and Power Supply All AC power supplies 12 feet (3.5 m) Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 6: Rack And Cabinet Requirements

    These cables must not block access to any removable chassis modules or block airflow into or out of the chassis. Route the cables through the cable management frames on the left and right sides of the chassis. Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 7: Clearance Requirements

    For the clearances required for an installation of this chassis, see the following figure. Figure 1: Clearances Required Around the Chassis Chassis Rear service clearance required to replace fan trays and fabric modules Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...
  • Page 8 I/O module handles (keep this area clear of rack, cable management, and other components that can prevent full rotation of the ejector levers) No right side clearance required (no airflow on right side) Cisco Nexus 9504 NX-OS Mode Switch Hardware Installation Guide...

Table of Contents