Performance Data - 5 Ton - Coleman ECHELON AC21 Series Technical Manual

Split system air conditioners
Table of Contents

Advertisement

PERFORMANCE DATA - 5 TON

Outdoor units must be applied with Johnson Controls Unitary Products indoor coils, so Condenser Only data is not provided.
COOLING PERFORMANCE DATA - HIGH
AIR CONDITIONER MODEL NO.
IDCFM
AIR TEMP.
ENTERING
ID DB (°F)
OUTDOOR UNIT (°F)
ID WB (°F)
T.C.
55
S.C.
KW
T.C.
65
S.C.
KW
T.C.
75
S.C.
KW
T.C.
85
S.C.
KW
T.C.
95
S.C.
KW
T.C.
105
S.C.
KW
T.C.
115
S.C.
KW
T.C.
125
S.C.
KW
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COIL MULTIPLIERS - 5 TON
Air Handler
Coil
AVV61CE421
AVV61DE421
MVC20DN21
CM61DE4A1
FURNACE MULTIPLIERS - 5 TON
Furnaces
Coil
TM8V100C20MP12C
CM61CE4A1
TM8V120C20MP12C
CM61CE4A1
TM9V100C20MP12C
CM61CE4A1
TM9V120D20MP12C
CM61DE4A1
Subject to change without notice. Published in U.S.A.
Copyright © 2019 by Johnson Controls. All rights reserved.
NOTICE
AC21B6021S
1530
80
80
75
80
80
57
62
62
67
72
51.3
53.7
54.6
58.4
59.8
34.7
35.5
35.7
39.4
40.2
2.60
2.58
2.58
2.56
2.54
51.3
53.8
54.6
58.9
62.7
34.7
36.1
36.3
40.1
42.4
3.13
3.13
3.13
3.13
3.13
51.3
53.8
54.6
59.3
65.5
34.7
36.7
36.8
40.8
44.6
3.65
3.69
3.68
3.70
3.72
51.3
53.9
54.7
59.8
65.5
35.3
37.3
37.4
41.3
45.3
4.49
4.52
4.52
4.56
4.60
51.3
53.9
54.8
60.2
65.5
35.9
37.9
37.9
41.7
45.9
5.33
5.36
5.36
5.42
5.47
47.6
49.8
50.1
55.5
61.3
34.1
35.6
35.8
39.5
43.3
5.90
5.94
5.94
6.00
6.08
44.2
45.8
46.0
52.1
56.5
31.3
32.8
32.9
36.7
40.4
6.50
6.52
6.52
6.59
6.68
39.5
41.8
41.4
46.7
52.2
28.4
30.1
30.4
33.7
37.4
7.15
7.21
7.19
7.27
7.34
T.C.
S.C.
KW
1.00
0.98
1.04
1.00
1.00
1.00
1.00
0.99
1.00
T.C.
S.C.
KW
1.00
0.97
1.04
1.00
0.97
1.04
0.99
0.98
1.06
1.00
0.96
1.04
York International Corp.
5005 York Drive
Norman, OK 73069
1800
80
80
75
80
80
57
62
62
67
72
52.9
55.0
55.6
58.6
59.6
36.0
36.8
36.9
39.6
40.1
2.67
2.66
2.66
2.63
2.62
53.0
55.1
55.6
59.5
62.9
36.1
37.2
37.3
40.5
42.6
3.21
3.22
3.22
3.21
3.22
53.1
55.1
55.6
60.5
66.2
36.2
37.6
37.7
41.5
45.1
3.76
3.78
3.78
3.79
3.82
53.2
55.2
55.7
60.8
66.5
36.6
38.2
38.2
42.0
45.9
4.59
4.62
4.62
4.65
4.69
53.3
55.3
55.8
61.1
66.9
37.1
38.8
38.7
42.5
46.8
5.42
5.46
5.46
5.51
5.57
49.5
51.0
51.1
56.6
62.7
35.5
36.5
36.5
40.2
44.2
6.01
6.04
6.03
6.10
6.17
45.8
47.1
46.9
53.3
57.7
32.7
33.8
33.6
37.5
41.2
6.59
6.60
6.61
6.68
6.77
41.1
42.9
42.5
47.5
53.1
29.7
31.0
31.0
34.3
38.0
7.24
7.29
7.28
7.36
7.43
FURNACE MULTIPLIERS - 5 TON (Continued)
Furnaces
Coil
TMLV100C20MP12C
CM61CE4A1
TMLV120C20MP12C
CM61CE4A1
TP9C100C20MP13C
CM61CE4A1
TP9C120D20MP13C
CM61DE4A1
TPLC100C20MP13C
CM61CE4A1
TPLC120C20MP13C
CM61CE4A1
CP9C100C20MP13C
CM61CE4A1
CP9C120D20MP13C
CM61DE4A1
CPLC100C20MP13C
CM61CE4A1
CPLC120C20MP13C
CM61CE4A1
1980
80
80
75
80
80
57
62
62
67
72
54.4
56.3
56.5
58.7
59.4
37.3
38.0
38.0
39.7
40.0
2.74
2.73
2.73
2.71
2.70
54.7
56.4
56.6
60.2
63.1
37.5
38.2
38.3
41.0
42.8
3.30
3.30
3.30
3.29
3.31
54.9
56.4
56.6
61.7
66.8
37.6
38.4
38.5
42.2
45.5
3.86
3.87
3.87
3.88
3.91
55.1
56.5
56.7
61.8
67.5
37.9
39.0
39.0
42.8
46.6
4.69
4.71
4.71
4.75
4.79
55.3
56.6
56.7
61.9
68.2
38.2
39.6
39.4
43.3
47.7
5.52
5.55
5.55
5.61
5.67
51.4
52.2
52.1
57.6
64.0
36.8
37.3
37.2
40.8
45.1
6.12
6.14
6.13
6.20
6.27
47.3
48.3
47.7
54.4
58.8
34.0
34.8
34.3
38.3
41.9
6.68
6.69
6.70
6.77
6.87
42.6
44.0
43.6
48.2
53.9
30.9
31.9
31.6
34.8
38.6
7.34
7.37
7.36
7.45
7.52
T.C.
S.C.
KW
1.00
0.97
1.04
1.00
0.97
1.04
0.99
0.98
1.06
1.00
0.96
1.04
1.00
0.97
1.04
1.00
0.97
1.04
0.99
0.98
1.06
1.00
0.96
1.04
1.00
0.97
1.04
1.00
0.97
1.04
5443702-CTG-C-0919
Supersedes: 5443702-CTG-B-0418