ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Quick Links

®
Relion
615 series
Transformer Protection and Control
RET615
IEC 60870-5-103 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion 615 series Transformer Protection and Control RET615 IEC 60870-5-103 Point List Manual...
  • Page 3 Document ID: 1MRS756883 Issued: 2012-05-11 Revision: C Product version: 4.0 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 IEC 60870-5-103 data mappings........11 Overview...................11 Supported functions................11 Point list for RET615 Ver.4.0 TE01-08..........13 Indications and controls...............13...
  • Page 8 Table of contents LD0.MAPGAPC4 Multipurpose analog protection function (4)................19 LD0.MAPGAPC5 Multipurpose analog protection function (5)................19 LD0.MAPGAPC6 Multipurpose analog protection function (6)................19 LD0.XRGGIO130 Alarm and warning........20 LD0.PHPTOV3 Phase overvoltage protection - stage 3..20 LD0.PHPTOV2 Phase overvoltage protection - stage 2..20 LD0.PHPTOV1 Phase overvoltage protection - stage 1..20 LD0.PHPTUV3 Phase undervoltage protection - stage 3.....................21 LD0.PHPTUV2 Phase undervoltage protection - stage...
  • Page 9 Table of contents LD0.PHLPTOC1 Phase overcurrent protection - low stage 1..................26 LD0.PHLPTOC2 Phase overcurrent protection - low stage 2..................26 LD0.T2PTTR1 Thermal overload protection (2).....26 LD0.LREFPDIF1 Low-impedance restricted earth-fault protection (1)................27 LD0.HREFPDIF1 High-impedance restricted earth-fault protection (1)................27 LD0.TR2PDIF1 Transformer differential protection....27 LD0.CMMXU1 Phase currents (1) limit supervision....27 LD0.RESCMMXU1 Residual current (1) limit supervision................27...
  • Page 10 Table of contents COMMON ADDRESS of ASDU..........38 Selection of standard information numbers in monitor direction..................38 System functions in monitor directions........38 Status indications in monitor direction........38 Supervision indications in monitor direction......39 Earth fault indications in monitor direction......39 Fault indications in monitor direction........39 Auto-reclosure indications in monitor direction.......40 Measurands in monitor direction..........41 Generic functions in monitor direction........41...
  • Page 11: Section 1 Introduction

    Section 1 1MRS756883 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 12: Document Revision History

    B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual...
  • Page 13: Symbols And Conventions

    Section 1 1MRS756883 C Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS756883 C Introduction 1.4.3 Functions, codes and symbols Table 1: RET615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage PHLPTOC2 3I> (2) 51P-1 (2) Three-phase non-directional overcurrent PHHPTOC1 3I>>...
  • Page 15 Section 1 1MRS756883 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Multi-purpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4) MAP (4) MAPGAPC5 MAP (5) MAP (5) MAPGAPC6 MAP (6) MAP (6) Control Circuit-breaker control...
  • Page 17: Section 2 Iec 60870-5-103 Data Mappings

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview These tables show the default point definitions. The user is able to freely remap all these data. In that case PCM600 can provide an updated point list export of the new outlook.
  • Page 18 Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 TE01 TE02 TE03 TE04 TE05 TE06 TE07 TE08 TRPPTRC1 ● ● ● ● ● ● ● ● TRPPTRC2 ● ● ● ● ● ● ● ● ARCSARC1 (LV) ARCSARC2 (LV) ARCSARC3 (LV) MAPGAPC1 MAPGAPC2...
  • Page 19: Point List For Ret615 Ver.4.0 Te01-08

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings Point list for RET615 Ver.4.0 TE01-08 2.3.1 Indications and controls Table 3: Explanations of the indications and controls table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute.
  • Page 20: General Data(Fun=10) - 615-Specific

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU LD0.LEDPTRC1 .Op.general Global operate 10=Operate .Str.general Global start 10=Start 2.3.1.2 General Data(FUN=10) - 615-specific Table 5: General Data(FUN=10) - 615-specific IEC 61850 name SA name Description DPI value...
  • Page 21: Generaldata(10-2) - 615-Specific

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.3 GeneralData(10-2) - 615-specific Table 6: GeneralData(10-2) - 615-specific IEC 61850 name SA name Description DPI value ASDU LD0.CMSTA2 .RecR s.ctlVal Reset max.demands 2 10=Reset LD0.CMSTA2 2.3.1.4 LD0.MVGAPC1 Multipurpose binary inputs (1) Table 7: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name...
  • Page 22: Ld0.Srgapc1 Multipurpose Binary Outputs - Flip-Flop Resets (1)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.6 LD0.SRGAPC1 Multipurpose binary outputs - flip-flop resets (1) Table 9: LD0.SRGAPC1 Multipurpose binary outputs - flip-flop resets (1) IEC 61850 name SA name Description DPI value ASDU LD0.SRGAPC1 .Rs1.ctlVal Reset flip-flop 1 10=Reset .Rs2.ctlVal Reset flip-flop 2...
  • Page 23: Ld0.Spcggio2 Multipurpose Binary Outputs (2)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCS04.ctlVal Output control 4 10/01=On/Off .SPCS05.ctlVal Output control 5 10/01=On/Off .SPCS06.ctlVal Output control 6 10/01=On/Off .SPCS07.ctlVal Output control 7 10/01=On/Off .SPCS08.ctlVal Output control 8 10/01=On/Off .SPCS09.ctlVal Output control 9...
  • Page 24: Ld0.Nsptoc1 Negative-Sequence Overcurrent Protection (1)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.10 LD0.NSPTOC1 Negative-sequence overcurrent protection (1) Table 13: LD0.NSPTOC1 Negative-sequence overcurrent protection (1) IEC 61850 name SA name Description DPI value ASDU LD0.NSPTOC1 .Str.general START Stage1 start 10=Start .Op.general OPERATE Stage1 operate 10=Operate 2.3.1.11 LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
  • Page 25: Ld0.Mapgapc2 Multipurpose Analog Protection Function (2)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.15 LD0.MAPGAPC2 Multipurpose analog protection function (2) Table 18: LD0.MAPGAPC2 Multipurpose analog protection function (2) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC2 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.1.16...
  • Page 26: Ld0.Xrggio130 Alarm And Warning

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.20 LD0.XRGGIO130 Alarm and warning Table 23: LD0.XRGGIO130 Alarm and warning IEC 61850 name SA name Description DPI value ASDU LD0.XRGGIO130 XRGGIO130 Card .Wrn.stVal WARNING -Warning 10=Warning .Alm.stVal ALARM -Alarm 10=Alarm 2.3.1.21 LD0.PHPTOV3 Phase overvoltage protection - stage 3 Table 24: LD0.PHPTOV3 Phase overvoltage protection - stage 3...
  • Page 27: Ld0.Phptuv3 Phase Undervoltage Protection - Stage 3

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.24 LD0.PHPTUV3 Phase undervoltage protection - stage 3 Table 27: LD0.PHPTUV3 Phase undervoltage protection - stage 3 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTUV3 Stage 3 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 28: Ld0.Rovptov2 Residual Overvoltage Protection - Stage 2

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.28 LD0.ROVPTOV2 Residual overvoltage protection - stage 2 Table 31: LD0.ROVPTOV2 Residual overvoltage protection - stage 2 IEC 61850 name SA name Description DPI value ASDU LD0.ROVPTOV2 .Op.general OPERATE Stage 2 operate 10=Operate .Str.general START...
  • Page 29: Ld0.Xggio110 Physical Binary I/O Signals (Status Only)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.32 LD0.XGGIO110 Physical binary I/O signals (status only) Table 35: LD0.XGGIO110 Physical binary I/O signals (status only) IEC 61850 name SA name Description DPI value ASDU LD0.XGGIO110 .Ind1.stVal X110-Input 1 10/01=On/Off .Ind2.stVal X110-Input 2 10/01=On/Off .Ind3.stVal...
  • Page 30: Ld0.Arcsarc1 Fault Arc Protection - Stage 1

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.35 LD0.ARCSARC1 Fault arc protection - stage 1 Table 38: LD0.ARCSARC1 Fault arc protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.ARCSARC11 .FADet.stVal ARC_FLT_DE T Arc detected 10=Detect LD0.ARCPTRC11 .Op.general...
  • Page 31: Ld0.Eflptoc2 Non-Directional Earth-Fault And Sensitive Earth-Fault Protection - Low Stage 2

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.39 LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault protection - low stage 2 Table 42: LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault protection - low stage 2 IEC 61850 name SA name Description DPI value ASDU LD0.EFLPTOC2 Low (2) stage...
  • Page 32: Ld0.Phhptoc1 Phase Overcurrent Protection - High Stage 1

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.43 LD0.PHHPTOC1 Phase overcurrent protection - high stage 1 Table 46: LD0.PHHPTOC1 Phase overcurrent protection - high stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHHPTOC1 High stage (1) .Str.phsA -phsA start 10=Start...
  • Page 33: Ld0.Lrefpdif1 Low-Impedance Restricted Earth-Fault Protection (1)

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.47 LD0.LREFPDIF1 Low-impedance restricted earth-fault protection (1) Table 50: LD0.LREFPDIF1 Low-impedance restricted earth-fault protection (1) IEC 61850 name SA name Description DPI value ASDU LD0.LREFPDIF1 .Str.general START Stage start 10=Start .Op.general OPERATE Stage operate 10=Operate 2.3.1.48...
  • Page 34: Ld0.Cmmxu2 Phase Currents (2) Limit Supervision

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.52 LD0.CMMXU2 Phase currents (2) limit supervision Table 55: LD0.CMMXU2 Phase currents (2) limit supervision IEC 61850 name SA name Description DPI value ASDU LD0.CMMXU2 .HiAlm.stVal HIGH_ALARM High alarm 10=Alarm .HiWrn.stVal HIGH_WARN High warning 10=Warning .LoWrn.stVal...
  • Page 35: Ld0.Sscbr1 Circuit Breaker (1) Condition Monitoring

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.55 LD0.SSCBR1 Circuit breaker (1) condition monitoring Table 58: LD0.SSCBR1 Circuit breaker (1) condition monitoring IEC 61850 name SA name Description DPI value ASDU LD0.SSCBR1 .RsAccAPwr.ctlVal RST_IPOW Accumul. energy reset 10=Reset .RsCBWear.ctlVal RST_CB_WEAR CB life/op.counters reset 10=Reset...
  • Page 36: Ctrl.dcxswi2 Disconnector (2) - Controllable Object

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.57 CTRL.DCXSWI2 Disconnector (2) - controllable object Table 60: CTRL.DCXSWI2 Disconnector (2) - controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCCILO2 .EnaOpn.stVal ENA_OPEN Open enabled 10=Enabled .EnaCls.stVal ENA_CLOSE Close enabled 10=Enabled .ItlByPss.stVal...
  • Page 37: Ctrl.dcsxswi2 Disconnector (2) - Non-Controllable Object

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings 2.3.1.60 CTRL.DCSXSWI2 Disconnector (2) - non-controllable object Table 63: CTRL.DCSXSWI2 Disconnector (2) - non-controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCSXSWI2 .Pos.stVal POSITION Disconnector 2 pos 10/01=Close/Open 2.3.1.61 CTRL.DCSXSWI3 Disconnector (3) - non-controllable object Table 64: CTRL.DCSXSWI3 Disconnector (3) - non-controllable object...
  • Page 38: Class 2 Data Measurands

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCSO8.stVal LED 8 state 10=On .SPCSO9.stVal LED 9 state 10=On .SPCSO10.stVal LED 10 state 10=On .SPCSO11.stVal LED 11 state 10=On 2.3.2 Class 2 data measurands Class 2 data measurands use ASDU type 9, function type 10 and information number 236 for frame 6 and 237 for frame 7.
  • Page 39: Class 2 Private Measurand Data (6 And 7) For Ret615

    Section 2 1MRS756883 C IEC 60870-5-103 data mappings Table 68: Explanations of the class 2 data measurands table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
  • Page 40 Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (T-a) xi (T-b) .Tmp.mag Temperature 1000 .TmpRl.mag Relative temperature 1000 LD0.CMSTA1 Demand currents (1) LD0.CMSTA1 Phase-current demands .AvAmpsA.mag -phsA magnitude .AvAmpsB.mag -phsB magnitude .AvAmpsC.mag -phsC magnitude LD0.CMSTA2 Demand currents (2) LD0.CMSTA2 Phase-current demands...
  • Page 41 Section 2 1MRS756883 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (T-a) xi (T-b) .phsB.cVal.mag Bias current B .phsC.cVal.mag Bias current C LD0.XRGGIO130 RTD Input data LD0.XRGGIO130 .AnIn1.mag RTD input 1 10000 .AnIn2.mag RTD input 2 10000 .AnIn3.mag RTD input 3 10000...
  • Page 43: Section 3 Interoperability Profile For 615 Series Iec 60870-5-103

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 Section 3 Interoperability profile for 615 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard.
  • Page 44: Application Layer

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
  • Page 45: Supervision Indications In Monitor Direction

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
  • Page 46: Auto-Reclosure Indications In Monitor Direction

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
  • Page 47: Measurands In Monitor Direction

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I , P, Q, f L1,2,3 L1,2,3...
  • Page 48: Basic Application Functions

    Section 3 1MRS756883 C Interoperability profile for 615 series IEC 60870-5-103 3.3.5 Basic application functions ⃞ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in 615 series devices is 2.4.
  • Page 49: Section 4 Glossary

    Section 4 1MRS756883 C Glossary Section 4 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 60870-5-103 1. Communication standard for protective equipment 2.
  • Page 52 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...

This manual is also suitable for:

Relion ret615

Table of Contents