Power wiring diagram
3 phase 3wires 208-230V
MCCB+
MCCB+
ELB
ELB
or
ELCB
ELCB
Main unit
Single phase 2
wires 208-230V
MCCB +
ELB
or
ELCB
Grounding
Wired remote
controller
f Connect a power cable of the outdoor unit after checking that R-S-T (3 phase 3 wire) is properly connected .
f
f Malfunction may occur if one or more of the wires among R-S-T phases (3 Phases-3 Wires) are not connected properly .
f
(*Malfunction: Turning on/off, occurrence of error, consecutive reset)
f Communication cable between indoor and outdoor units and communication cable between outdoor units has no
f
polarity .
f Arrange the cables with a cable tie .
f
❋ ❋ ELCB and ELB must be installed since there is risk of electric shock or fire when they are not installed .
MCCB+
ELB
or
or
ELCB
Sub unit 1
Sub unit 2
Communication
cable (Outdoor unit ~
Outdoor unit)
Communication
cable (Outdoor unit ~
Indoor unit)
Grounding
Grounding
Wired
Wired
remote
remote
controller
controller
Main unit
Communication
cable (Outdoor unit ~
Indoor unit)
Sub unit
Communication
cable (Outdoor unit ~
Outdoor unit)
63