Operational temperature and humidity range
The table below indicates the temperature and humidity ranges the air
conditioner can be operated within. Refer to the table for efficient use.
Mode
Indoor temperature
Cool
Dry
Heat
f If the air conditioner operates in cooling mode for long period of time in high humidity area, dew may be formed.
f
f Extra heating load calculation is necessary when the air conditioner is going to be used for main heating source in
f
winter timer. In cold regions, we recommend to purchase the product designed for cold regions which has great heating
efficiency. (Please contact nearest service center for any inquiries.)
f The standardized temperature for heating is 7˚C. If the outdoor temperature drops to 0˚C or below, the heating capacity
f
can be reduced depending on the temperature condition.
Operating precautions
f Refrigerant used in air conditioner is non-toxic and non-flammable. However, when the air conditioner is installed in
f
small space, extra ventilation system is required in case of refrigerant leakage.
f When using H/R model, indoor units connected to same outdoor unit cannot be operated in different operation modes.
f
Indoor units should all be in Cooling (Cool/Dry/Fan mode) or Heating (Heat mode).
PAC Queen_AM048HNPDCH_EN_DB68-04906-00.indd 13
Outdoor temperature
18 °C ~ 32 °C
-5 °C ~ 48 °C
18 °C ~ 32 °C
-5 °C ~ 48 °C
Below 27 °C
-20 °C ~ 24 °C
ENGLISH-13
Indoor humidity
Relative humidity 80 % or less
-
-
2014-09-17 오후 3:19:35