Theben DIMAX 534 plus Manual
Theben DIMAX 534 plus Manual

Theben DIMAX 534 plus Manual

Universal dimmer

Advertisement

Quick Links

Universal dimmer
EN
DIMAX 534 plus
5340001
1. Basic safety information
WARNING
Danger of death through electric shock or fire!
Installation should only be carried out by a
¾
qualified electrician!
L Due to increasing technical progress, conspicuous features
in dimming behaviour or malfunctions cannot be ruled out
for dimmed lamps (in particular LEDs)
The dimmer is designed for installation on DIN top hat
rails (in accordance with EN 60715)
It conforms with IEC/EN 60669-2-1 if correctly installed
2. Proper use
The dimmer switches and dims the brightness of diffe-
rent lamps such as bulbs, high-voltage halogen lamps,
low-voltage halogen lamps (conventional or with elect-
ronic transformer), dimmable compact fluorescent lamps
(energy saving lamps) or dimmable lamps for 230 V as
well as for fans
The setting for brightness is carried out using the
dimmer on the button connected
The universal dimmer has a lamp-friendly "soft" on and
off system, automatic detection of the load type (not
in the case of ESL2 and LED2), overheating protection
against overload as well as a short-circuit protection.
For use in private and public buildings, in closed rooms
Disposal
Dispose of device in environmentally sound manner
3. Installation and connection
Mounting the dimmer
WARNING
Danger of death through electric shock or fire!
Installation should only be carried out by a
¾
qualified electrician!
307171 02
Disconnect power source
Ensure device cannot be switched on
Check absence of voltage
Earth and bypass
Cover or shield any adjacent live components
Mount the dimmer in the lower part of the distributor to
avoid an excessively high temperature during use.
In the case of a service line of >300 W keep an 8 mm dis-
tance to the right and left of the device.
Connecting the dimmer
Always operate electrical and conventional transformers
¾
with the minimum load specified by the manufacturer.
Use only dimmable compact fluorescent lamps / LED lamps
¾
as normal compact fluorescent lamps / LED lamps may be
destroyed.
When changing the lamps, switch off the power supply
¾
(at the fuse box) so that the automatic load detection is
reactivated.
Do not connect dimmer load connections (L´) in parallel.
¾
Do not by-pass or short-circuit the dimmer.
¾
Do not install any isolating or variable transformers before
¾
the dimmer.
Do not mix wound and electronic transformers in the
¾
installation.
Do not install wound transformers and compact fluorescent
¾
lamps / LED lamps mixed.
Do not connect push button with glow lamp.
¾
Correct, automatic load detection is only possible with a
¾
connected load.
Only use transformers approved by the manufacturer for
¾
dimmer operation.
Connection with 8 ... 230 V
Push buttons A1/A2 On/Off/Dim
LS 1 = Lighting scenario 1
LS 2 = Lighting scenario 2
LS 3 = Lighting scenario 3
AC/DC
8 ... 230 V
LS 1 LS 2 LS 3
9070825
Use compensation module 9070825 to prevent the LEDs
from afterglow or flickering.
Install the compensation module parallel to the
consumer.
!
Component can get hot!
A1
A2
+
B1
N
T
L'
L
N
L
1

Advertisement

loading

Summary of Contents for Theben DIMAX 534 plus

  • Page 1 † Universal dimmer Check absence of voltage † Earth and bypass † DIMAX 534 plus Cover or shield any adjacent live components † Mount the dimmer in the lower part of the distributor to 5340001 † avoid an excessively high temperature during use.
  • Page 2: Description Of Functions

    Connection with 230 V Position 3 Prog Teach in light settings and minimum brightness (only for CFL) L With several compact fluorescent lamps, an annoying flickering may occur when dimming in position 1. In this case, use position 2. † Carry out settings only with warm compact fluorescent †...
  • Page 3: Operation

    • 2. Snooze function (comfort function) Switch-off pre-warning: after expiry of the set time rapid • dimming down to 50% of the switch-in value. After 10 s, active in position 1, 2, 4, 6, 10 slow dimming down to minimum brightness within 30 s. The dimmer dims from the current dimming value up to the •...
  • Page 4: Technical Data

    Light is ON (with button: input A1/A2) Lighting scenario 1 can also be activated if buttons LS2 and LS3 are pressed simultaneously. This makes it possible to save using button LS1. 1 x short button < 1 s Switch off press Connection with diode module to several dimmers 1 x long button...
  • Page 5 8. Contact Theben AG Hohenbergstr. 32 72401 Haigerloch, Germany GERMANY Phone +49 7474 692-0 Fax +49 7474 692-150 Hotline Phone +49 7474 692-369 hotline@theben.de Addresses, telephone numbers, etc. www.theben.de...