Led Indication Priority - Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual

Table of Contents

Advertisement

3.20.2

LED indication priority

This section describes a priority for error messages stored in the LED display data (SD220 to SD227) in case of an
error.
(1) Displayed error messages and their priorities
In case of multiple errors, the error messages are displayed with the following conditions.
• A stop error is always set to the LED display data (SD220 to SD227).
• An operation continuation error is displayed according to the priority cause number described in this section.
Whether to indicate an error according to its priority using LED can be selected. (Set the priority using
special registers, SD207 to SD209.)
• When errors having the same priority occur simultaneously, the error detected first is displayed.
The priority is determined with the special registers SD207 to SD209 as follows.
15
12 11
to
SD207
Priority 4
Priority 8
SD208
SD209
Ignored
222
to
8 7
to
4 3
Priority 3
Priority 2
Priority 1
Factor number setting area
Priority 6
Priority 7
Priority 5
Factor number setting area
Priority 10
Factor number setting area
to
0 bits
SD207
SD208
SD209
Priority 9
Default value of factor number
15
to
2
4
3
1
7
6
8
5
0
0
A
9
0 bits

Advertisement

Table of Contents
loading

Table of Contents