12 - OPTIONS
Units with hydraulic module low pressure (116A)
30KAV-ZE /
Minimum flow rate
30KAVPZE
0350
0400
0450
0500
0550
0600
(1) See unit without hydraulic module in section 4.12.
Units with high pressure hydraulic module (116W)
30KAV-ZE /
Minimum flow rate
30KAVPZE
0350
0400
0450
0500
0550
0600
(1) See unit without hydraulic module in section 4.12.
68
Maximum flow rate
(1)
(l/s)
(l/s)
(1)
35,2
(1)
34,2
(1)
34,2
(1)
34,2
(1)
52,8
(1)
52,8
Maximum flow rate
(1)
(l/s)
(l/s)
(1)
34,2
(1)
34,6
(1)
34,6
(1)
34,6
(1)
69,4
(1)
69,4
12.1.4 - Cavitation protection
To  ensure  the  durability  of  pumps  fitted  within  the  integrated 
(1)
hydraulic modules, the control algorithm for units includes
protection against cavitation. It is therefore necessary to ensure
a minimum pressure at the pump inlet both when shut down and
during operation. A pressure below the predefined threshold will 
prevent unit start-up or will cause an alarm and shutdown. Before
complete shutdown following an alarm, the user interface will give
an advance warning that this threshold has been exceeded.
To obtain an adequate pressure, it is recommended:
■ That the hydraulic circuit is pressurized between 100 kpa
(1 bar) and 400 kpa (4 bar) maximum at the pump inlet,
■ That the hydraulic circuit is cleaned when filled with water or 
when modified,
(1)
■ That the screen filter is cleaned regularly.