Rigid Pipe Venting Arrangements - Vertical Terminations - UltraGlow G36D Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

The G36D is approved for a maximum 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset
using two 90
elbows (two 45
o
o
Natural Gas, as per diagram 1.
The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal
offset using two 90
elbow (two 45
o
and Natural Gas, as per diagram 2.
Vent must be supported at offsets
Maintain clearances as listed in the"Clearances" section.
Firestops are required at each fl oor level and whenever passing through a wall.
Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part # 510-994).
Note: UltraGlow
Note: UltraGlow
Note: UltraGlow Direct Vent System (Flex) is only approved for horizontal terminations.
Direct Vent System (Flex) is only approved for horizontal terminations.
®
®
®
®
16
(Propane & Natural Gas)
elbows equal one 90
elbow) with Rigid Pipe vent systems for Propane and
o
elbows equal one 90
elbow) with Rigid Pipe vent systems for Propane
o
o
Diagram 1
UltraGlow
G36D Zero Clearance Direct Vent Gas Fireplace
G36D Zero Clearance Direct Vent Gas Fireplace
®
®
®
Diagram 2