SPRINKLERS ARE FRAGILE - HANDLE WITH CARE!
Always keep sprinklers in a cool dry place.
Protect sprinklers during storage, transport and handling as well as before, during and after installation. Refer
to Viking's Care and Handling of Sprinklers Bulletin
Proper transit, storage and installation of sprinklers in a high-heat environment is a must. Care should be
taken to prevent sprinklers from being exposed to ambient heat conditions in excess of those referenced in
installation standards.
Do not stage or store sprinklers on the job site in advance in a non-conditioned space prior to installation.
Keep sprinklers in the original packaging and check temperature indicators on box label prior to installation.
If the indicator has turned black, DO NOT install any product contained in the box. Refer to Viking product
return policies.
Temperatures exceeding the maximum ambient temperature of the sprinkler temperature-rating during
storage, transport, handling and installation must be avoided.
Per NFPA standards 13, 13R, and 13D, sprinklers installed where maximum ambient temperatures are
at or over 101 °F (38 °C ) through 150 °F (66 °C) shall be intermediate temperature-rated sprinklers.
Additionally, if sprinklers are installed in an unventilated concealed space under an uninsulated roof or in
an unventilated attic, they shall be of intermediate temperature classification.
Sprinklers installed where ambient temperatures are at or below 100 °F (38 °C) may be either ordinary or
intermediate temperature-rated sprinklers. Refer to NFPA standards 13R 6.2.3.1 and 13D 7.5.6.1.
Rough-in of sprinkler piping during hot weather conditions should not include the installation of sprinklers
unless reasonable ambient temperatures can be maintained. Ambient temperatures that are considered
when choosing the temperature rating for a sprinkler should take into account the range of ambient
temperatures that are expected from installation through establishment and maintenance of temperature
in a conditioned space. Appropriate insulation may be considered. Example: An ordinary temperature
sprinkler should not be exposed to maximum ambient temperature higher than 100 °F (38 °C) or more.
Refer to NFPA 13, Table 6.2.5.1, NFPA 13R, 6.2.3.1 and NFPA 13D, 7.5.6.1.
CPVC fire sprinkler products exposed to high ambient temperatures (e.g. installed in unventilated, concealed
spaces such as attics) should be insulated to maintain a cooler environment. Refer to Viking Plastics
Installation and Design Manual,
Protect all sprinklers and connecting CPVC piping in attic spaces and unvented concealed spaces from
excessive heat exposure above 100 °F (38 °C). To separate excessive attic heat, properly tent and fully
insulate all pipe in unconditioned spaces.
Pressure relief valves should be installed on wet sprinkler systems where there is a risk of over-pressurization
of a checked water supply, due to thermal expansion. Refer to NFPA 13, 7.1.2.1 and NFPA 13D, A.5.2.2.2.
Fire sprinkler systems should be installed per current referenced editions of building codes and installation
standards adopted in the jurisdiction where work is being performed.
Hot weather condition is defined as temperatures that can reach the maximum ambient temperature-rating of the sprinkler.
1
Clicking on blue hyperlink will open referenced document.
2
Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers that have been
dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that have been painted in the
field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with the installation standards. Do not clean
sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives or solvents on sprinklers or their operating elements.
Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions.
For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.
vikinggroupinc.com.
Form No. F_080415
18.10.11
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Visit the Viking website for the latest edition of this technical data page.
Form No. F_091699
Form No. F_080712
, for care and handling procedures.
2
Rev 16.3.P65
BULLETIN
.
2
WARNING
BEST PRACTICES FOR
RESIDENTIAL SPRINKLER
HANDLING & INSTALLATION
(Heat exposure)
(Unconditioned at rough-in)
INCORRECT
(Exposed piping)
INCORRECT
(No pressure relief valve)
Page 1 of 1
INCORRECT
INCORRECT