To Fix The Fluorinated Greenhouse Gases Label; To Check For Refrigerant Leaks After Charging - Daikin Multi+ R32 Split Series Installer's Reference Manual

Table of Contents

Advertisement

8
|
Charging refrigerant

8.7 To fix the fluorinated greenhouse gases label

8.8 To check for refrigerant leaks after charging

Installer reference guide
46
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
4
"16.2 To pump
down" [
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
f
GWP: XXX
2
1
+
1
GWP × kg
1000
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total refrigerant charge
expressed as tonnes CO
f GWP = Global Warming Potential
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
INFORMATION
Applicable ONLY for combination with indoor units CVXM-A9, FVXM-A9.
All field made refrigerant joints must be tested for tightness.
No leak shall be detected with a test method that has a sensitivity of 5  grams
refrigerant per year or better, at a pressure of at least 0.25  times the maximum
working pressure (see "PS High" on the unit name plate).
 70] for more details.
a
kg
b
1
=
kg
c
2
=
d
kg
2
=
=
e
tCO
eq
2
equivalent.
2
equivalent.
2
equivalent tonnes: GWP value of the
2
4P708645-1 – 2022.09
4MWXM-A9
R32 Split series