Power Specification Of I/O Expansion Cabinet; Compaq Alphaserver Gs320 Environmental Specifications - Compaq ALPHA GS320 Information Manual

Compaq server user manual
Hide thumbs Also See for ALPHA GS320:
Table of Contents

Advertisement

7.3 Power Specification of I/O Expansion Cabinet

Power Spec
Voltage, Vrms
Frequence, Hz
Phase
Power Plug, Quantity
Phase current, Arms
Total VA
Total power, watts
Heat output, Btu/hr

7.4 Compaq AlphaServer GS320 Environmental Specifications

Variable
Temperature
Operating
Non-operating (storage)
Relative humidity (non-condensing)
Operating
Non-operating (storage)
Maximum altitude
Operating
Non-operating (storage)
Minimum Clearances
Front operating
Front Service
Rear Operating
Rear Service
Left side operating
Left side service
Right side operating
Right side service
U.S./Canada
120
50-60
1
L5-30P, 2
22
4,800
4,750
16,200
Specifications
5 to 35 C (41 to 95 F)
-40 to 66 C (-40 to 151 F)
10 to 90%
10 to 95%
3050m (10,000ft)
12,200m (40,000ft)
75 cm (29.5 in)
75 cm (29.5 in)
15 cm (6.0 in)
75 cm (29.5 in)
none
75 cm (29.5 in)
none
none
Japan
200
50-60
1
L6-30P, 1
24
4,800
4,750
16,200
Europe
220/240
50-60
1
IEC309 3P 32A, 1
22
4,800
4,750
16,200
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alphaserver gs320

Table of Contents