Honeywell Notifier NFS-320/E/C Operation Manual page 2

Fire alarm control panel
Table of Contents

Advertisement

Fire Alarm System Limitations
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! 
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! 
An automatic fire alarm system—typically made up of 
An automatic fire alarm system
smoke detectors, heat detectors, manual pull stations, audible
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a develop-
notification capability—can provide early warning of a
ing fire.
ing fire. Such a system, however
Such a system, however, does not assure
against property damage or loss of life resulting from a fire.
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations, State and local codes, and the recommen-
dations contained in the Guide for Proper Use of System
dations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
Smoke Detectors, which is made available at no charge to all
installing dealers. A study by the
installing dealers.
A study by the Federal Emergency Man-
agement Agency (an agency of the United States government)
agement Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm systems are designed to pro-
35% of all fires.
While fire alarm systems are designed to pro-
vide early warning against fire, they do not guarantee warning
vide early warning against fire, they do not guarantee warning
or protection against fire.
or protection against fire. A fire alarm system may not provide
A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a
timely or adequate warning, or simply may not function, for a
variety of reasons:
variety of reasons:
Smoke detectors may not sense fire where smoke cannot
Smoke detectors
may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
reach the detectors such as in chimneys, in
roofs, or on the other side of closed
roofs, or on the
other side of closed doors.
also may not sense a fire on another level
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a first-
A second-floor detector, for example, may not sense a first-
floor or basement fire.
floor or basement fire.
Particles of combustion or "smoke" from a developing fire
Particles of combustion or "smoke"
may not reach the sensing chambers of smoke detectors
may not reach the sensing chambers of smoke detectors
because:
because:
• •
Barrie
Barriers such
rs such as clo
as closed o
sed or pa
r partiall
chimneys may inhibit particle or
chimneys may inhibit particle or smoke flow.
• •
Smoke partic
Smoke
particles ma
les may beco
y become "c
the ceiling or upper walls where detectors are located.
the ceiling or upper walls where detectors are located.
• •
Smoke
Smoke parti
particles m
cles may be
ay be blown
blown away
outlets.
outlets.
• •
Smoke partic
Smoke
particles ma
les may be
y be drawn
drawn into
reaching the detector.
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed
smoke detectors.
Smoke detectors are designed to alarm at
various levels of smoke density. . If such density levels are not
various levels of smoke density
created by a developing fire at the location of detectors, the
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
Smoke detectors, even when
limitations. Detectors that
limitations.
Detectors that have photoelectronic
have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
chambers tend to detect smoldering fires better than flaming
fires, which have little visible
fires, which have little visible smoke.
smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in
better than smoldering fires.
Because fires develop in different
ways and are often unpredictable in their growth, neither type
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector 
of detector is necessarily best and a given type of detector 
may not provide adequate warning of a fire.
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of 
explosions (caused by escaping gas, improper storage of 
flammable materials, etc.).
flammable materials, etc.).
2 2
—typically made up of 
develop-
, does not assure protection
protection
recommen-
Federal Emergency Man-
or behind walls, on
doors. Smoke detectors
Smoke detectors
or floor of a building.
from a developing fire
rtially clos
y closed do
ed doors, w
ors, walls,
alls, or 
or 
smoke flow.
me "cold,"
old," strati
stratify fy, and
, and not re
not reach
ach
away from d
from detecto
etectors by
rs by air 
air 
into air r
air return
eturns befo
s before re
to alarm at
If such density levels are not
working properly, have sensing
sensing
Detectors that have ion-
different
Heat detectors do not sense particles of combustion and
Heat detectors
do not sense particles of combustion and
alarm only when heat on their sensors increases at a predeter-
alarm only when heat on their sensors increases at a predeter-
mined rate or reaches a predetermined
mined rate or
reaches a predetermined level.
heat detectors may be subject to reduced s ensitivity over time.
heat detectors may be subject to reduced s
For this reason, the rate-of-rise feature of each detector 
For this reason, the rate-of-rise feature of each detector 
should be tested at least once per year by a qualified fire pro-
should be tested at least once per year by a qualified fire pro-
tection specialist.
tection specialist. Heat detectors are
Heat detectors are designed to
property, not life.
property, not life.
IMPORTANT! Smoke
IMPORTANT!
Smoke detectors
detectors must be installed in the
same room as the control panel and in rooms used by the sys-
same room as the control panel and in rooms used
tem for the connection of alarm transmission wiring, communi-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or p
cations, signaling, and/or power.
ower. If detectors are not so
located, a developing fire may damage the alarm system, crip-
located, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
pling its ability to report a fire.
Audible warning devices
Audible warning devices such as bells may not alert people
such as bells may not alert people
if these devices are located on the other side of closed or 
if these devices are located on the other side of closed or 
partly open doors or are located on another floor of a building.
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or 
Any warning device may fail to alert people with a disability or 
those who have recently consumed drugs, alcohol or medica-
those who have recently consumed drugs, alcohol or medica-
tion.
tion. Please
Please note
note that:
that:
• •
Str
Strobes
obes can, u
can, under
nder certa
certain ci
in circumsta
in people with conditions such as epilepsy.
in people with conditions such
• •
Studies
Stu
dies have s
have shown
hown that c
that certai
ertain peo
hear a fire alarm signal, do not respond or comprehend the
hear a fire alarm signal, do not
meaning of the signal.
meaning of the sign
al. It is the property
It is the property owner's responsi-
bility to conduct fire drills and other training exercise to
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
on the proper reaction to alarm signals.
• •
In rar
In rare ins
e instance
tances, the
s, the sound
sounding o
ing of a w
cause temporary or permanent hearing loss.
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
A fire alarm system
will not operate without any electrical
power.
power. If AC power fails, the system will
If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
been properly maintained and
replaced regularly.
Equipment used in the system may not be technically com-
Equipment used in the system
patible with the control panel. It is essential to use only equip-
patible with the control panel.
It is essential to use only equip-
ment listed for service with your control panel.
ment listed for service with your control panel.
Telephone lines
Telephone lines needed to transmit alarm signals from a
needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
phone line failure, backup radio transmission systems are rec-
ommended.
ommended.
The most common cause
The most common cause of fire alarm malfunction is inade-
of fire alarm malfunction is inade-
quate maintenance.
quate maintenance. T T o keep the entire fire alarm system in
o keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per 
excellent working order, ongoing maintenance is required per 
the manufacturer's recommendations, and UL and NFPA stan-
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of NFP
dards.
At a minimum, the requirements of NFPA 72 shall be
followed.
followed. Environments with large
Environments with large amounts of dust, dirt
high air velocity require more frequent ma
high air velocity
require more frequent maintenance.
tenance agreement should be arranged through the local man-
tenance agreement should be arranged through the local man-
ufacturer's representative.
ufacturer's representative. Maintenance should
Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
should be performed by authorized professional fire alarm
installers only. . Adequate written records
installers only
Adequate written records of all inspections
should be kept.
should be kept.
 NFS-320/E/C Operations Manual — 
 NFS-320/E/C Operations Manual — P/N
level. Rate-of-rise
Rate-of-rise
ensitivity over time.
designed to protect
protect
must be installed in the
by the sys-
If detectors are not so
rcumstances,
nces, cause
cause seizur
seizures
es
as epilepsy.
n people,
ple, even
even when t
when they
hey
respond or comprehend the
owner's responsi-
f a warning
arning device
device can
can
operate from standby
may not be technically com-
A 72 shall be
amounts of dust, dirt or 
or 
intenance. A main-
A main-
be scheduled
of all inspections
Limit-C-9-2005
Limit-C-9-2005
P/N 52747:A
52747:A 12/28/2006
12/28/2006

Advertisement

Table of Contents
loading

Table of Contents