Relief Valve - Maintenance and Testing

The relief valve manufacturer requires that under normal operating conditions a
"try lever test" must be performed quarterly . Under severe service conditions, or
if corrosion and/or deposits are noticed within the valve body, you must test more
often . Also perform a "try lever test" at the end of any non-service period .
Test at or near maximum operating pressure by holding the test lever fully open
for at least 5 seconds to flush the valve seat free of sediment and debris. Then
release the lever and permit the valve to snap shut .
If the lever does not activate, or there is no evidence of discharge, discontinue
use of equipment immediately, and contact a licensed contractor or qualified
service personnel .
If the relief valve does not completely seal, and fluid continues to leak from
the discharge pipe, perform the test again to try and flush any debris that may
be lodged in the valve . If repeated attempts fail to stop the leakage, contact a
licensed contractor or qualified service personnel to replace the valve.
While performing a "try lever test", a quantity of heat transfer fluid will be
discharged from the piping system, and the system pressure will drop. This fluid
must be replaced . We highly recommend using a system pressurization unit
such as an Axiom Industries model MF200 to refill and pressurize your system.
Capture the discharged fluid in a container and recycle it by returning it to the
system feeder unit . This is particularly important when your system contains
treatment chemicals or glycol solutions . If the system employs plain water, turn
on the unit's auto fill valve to recharge the lost fluid.