TABLE 14 581030-01
LGM/LCM102U Reheat
Circuit 1
Outdoor
Dis­
Coil
Suction
Entering
charge
+5 psig
Air Temp
+10 psig
655 F
264
755 F
301
855 F
349
955 F
399
1055 F
450
1155 F
508
TABLE 15 581031-01
LGM/LCM120U No Reheat
Circuit 1
Outdoor
Dis­
Coil
Suction
Entering
charge
+5 psig
Air Temp
+10 psig
655 F
258
755 F
296
855 F
337
955 F
383
1055 F
439
1155 F
490
TABLE 16 581032-01
LGM/LCM120U Reheat
Circuit 1
Outdoor
Coil
Dis­
Suction
Entering
charge
+5 psig
Air Temp
+10 psig
655 F
272
755 F
309
855 F
350
955 F
396
1055 F
452
1155 F
503
TABLE 17 581033-01
LGM/LCM150U No Reheat
Circuit 1
Outdoor
Coil
Dis­
Suction
Entering
charge
+5 psig
Air Temp
+10 psig
655 F
267
755 F
308
855 F
355
955 F
399
1055 F
448
1155 F
503
Circuit 2
Dis­
Suction
charge
+5 psig
+10 psig
140
266
137
139
300
139
141
341
141
144
390
144
146
440
147
149
494
150
Circuit 2
Dis­
Suction
charge
+5 psig
+10 psig
132
263
131
137
302
133
139
344
135
141
389
137
142
438
140
145
494
143
Circuit 2
Dis­
Suction
charge
+5 psig
+10 psig
131
255
133
135
294
135
138
335
137
139
381
139
141
430
142
144
485
145
Circuit 2
Dis­
Suction
charge
+5 psig
+10 psig
122
270
113
128
313
120
133
363
127
136
407
130
139
456
132
142
510
136
TABLE 18 581034-01
LGM/LCM150U Reheat
Outdoor
Dis­
Coil
charge
Entering
+10 psig
Air Temp
655 F
313
755 F
353
855 F
401
955 F
445
1055 F
493
1155 F
548
Charge Verification - Subcooling Method - AHRI Test­
ing
1-
Attach gauge manifolds to discharge and suction lines. With
the economizer disabled, operate the unit in cooling mode
at high speed using the following mobile service app menu
path:
RTU MENU > SERVICE > COMPONENT TEST > COOLING
2- Use the liquid line pressure and a PT chart to determine
the saturated liquid temperature.
3- Measure the liquid line temperature at the condenser
outlet.
Subcooling Temperature = Liquid Saturated Tempera­
ture Minus Liquid Temperature.
4-
Refer to table 19 for subcooling temperatures. A subcooling
temperature greater than this value indicates an overcharge.
A subcooling temperature less than this value indicates an
undercharge.
SUBCOOLING TEMPERATURE
Unit
12°F + 1 (6.7°C +
092
17°F + 1 (9.4°C +
092 Reheat
11°F + 1 (6.1°C +
102
19°F + 1 (6.7°C +
102 Reheat
120
9°F + 1 (5.0°C + 0.5)
15°F + 1 (8.3°C +
120 Reheat
10°F + 1 (5.6°C +
150
22°F + 1 (12°C +
150 Reheat
Page 37
CIRCUIT 1
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
123
259
129
302
134
351
137
396
140
445
143
499
>COOL 4
TABLE 19
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
15°F + 1 (8.3°C + 0.5)
0.5)
15°F + 1 (8.3°C + 0.5)
0.5)
14°F + 1 (7.7°C + 0.5)
0.5)
14°F + 1 (7.7°C + 0.5)
0.5)
13°F + 1 (7.2°C + 0.5)
8°F + 1 (4.4°C + 0.5)
0.5)
11°F + 1 (6.1°C + 0.5)
0.5)
8°F + 1 (4.4°C + 0.5)
0.5)
Suction
+5 psig
113
121
127
130
133
137