9-Outdoor Fan Motor Fuse Block & Fuse
F10
STD SCCR 240V, 300V and higher rated SCCR units have
three line voltage fuses F10 provide overcurrent protection
to all condenser fans. The fuses are rated at 30A in all
208/230V units but 10A in the 208/230V 240U and 300U
models.
10-Transformer T4 ( J voltage)
All J volt units are equipped with a line voltage to 460V
3-phase transformer to power the indoor blower motor. T4
is mounted in the back panel of the compressor section.
Return Air Section
WIRELESS CONTROL
BOARD W4
Antenna Location
FIGURE 4
Cable Routing
(
)
FIGURE 5
11-Ultraviolet Germicidal Lamp (UVC)
Transformer T49
UVC transformer T49 is used by units of all voltages except
208/230V and 575V which are equipped with a UVC. The
auto voltage to 230VAC transformer is installed in the con­
trol box. The transformer has an output rating of 0.5 amps.
T49 transformer supplies 230VAC power to the UVC lamp.
12-Wireless Antenna
Wireless antenna is located above the return air compart­
ment of the unit. Figure 4 shows location and figure 5 shows
cable routing. Please follow the CORE Controller setup
guide included in the unit.
Smoke Detector
Page 14
Antenna
ANTENNA CABLE
ROUTING