Table of Contents

Advertisement

8.3 CABLE CONNECTION

SafeRing/SafePlus is equipped with external bushings which
comply with DIN47636T1 & T2/EDF HN 525-61 for termina-
tion of cables.
All bushings are situated in the same height from the floor and
are protected by the cable cover.
SafeRing / SafePlus can be supplied with the following bus-
hings for the various type of cubicles:
Bushings
C
Interface A
Interface C
X
Cable adapters
Adapters from following manufacturers are recommended:
ABB Kabeldon
Südkabel
Tyco Electronics Raychem
Power Systems
3M
Euromold
NKT cables
Please see supplier documentation for details.
DANGER
The manufacturer's installation instructions must
be followed. Be sure to lubricate the bushings
thoroughly with the silicone supplied.
Use only isolated cable connections.
Where cables are not connected, the earthing
switch must be locked in closed position or the
bushings must be fitted with dead end receptacles
before the unit is put into operation.
18
Type of module
F
V
D, De,
V20/25
X
X
X
X
X
Interface A with plug
200 series, In = 200A
Interface C with
M16 x 2 metric threads
400 series, In = 630A
Adjustable cable support bar (additional equipment).
Earthing bar
Cable clamp (additional equipment)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Safeplus

Table of Contents