8.3 ADC 2100 Adjustment
(5/7.3ECD, 4/6EFCD,
10/13/15EG, and 13/15EGZ
Models)
Figure 8-8 Advanced Digital Control (ADC 2100)
The controller is factory-set for the generator set voltage
and frequency and normally does not require
adjustment.
If adjustment is necessary, follow the
procedures in this section. Set the system voltage and
frequency and then adjust the voltage, gain, and engine
speed.
8.3.1

Configuration Mode Time Out

The controller will automatically exit the configuration
mode without saving any changes after about 1 minute if
no buttons are pressed.
procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.
52
Section 8 Reconnection/Adjustments
Start the configuration
8.3.2
Controller Software Version
Number
The application software for controller operation is
factory-loaded onto the Advanced Digital Control. At
times, it may be necessary to check the software version
number for troubleshooting purposes.
The controller's application software version number is
displayed on the LED screen during the key sequence to
enter the configuration mode, after the Select button has
been pressed and held for about five seconds. For
example, 01.00 will be displayed for software
version 1.00.
Note: The unit configuration (UC), engine type (EC),
and engine data input type (ED) are factory set
and should only be changed by an authorized
Kohler dealer/distributor. Incorrect settings will
make your unit non-functional.
8.3.3

Configuration Mode

Follow the instructions in Figure 8-11 to enter the
configuration mode.
Figure 8-9. An X in the Display column in Figure 8-11
indicates a number from 0 to 9.
Press the Select button to step through to the Save
mode as shown in Figure 8-13.
displayed, press the up arrow to save the new settings or
the down arrow to discard the changes and exit the
configuration mode without saving.
Pressing the Select button when SAVE is displayed
returns to the first parameter, system voltage/frequency
(Uu).
The settings are shown in
When SAVE is
TP-5982
4/06