Mechanical And Ambient Climatic Conditions For S7-300 Operation - Siemens SIMATIC RS 485 Manual

Hide thumbs Also See for SIMATIC RS 485:
Table of Contents

Advertisement

6.1.4

Mechanical and ambient climatic conditions for S7-300 operation

Operating conditions
S7-300 systems are designed for stationary use in weather-proof locations. The operating
conditions surpass requirements to DIN IEC 60721-3-3.
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Use with additional measures
The S7-300 may not be used under the conditions outlined below without taking additional
measures:
● at locations with a high degree of ionizing radiation
● in aggressive environments caused, for example, by
● in installations requiring special monitoring, for example
An additional measure could be an installation of the S7-300 in a cabinet or housing.
Mechanical environmental conditions
The table below shows the mechanical environmental conditions in the form of sinusoidal
oscillations.
Frequency band
10 Hz ≤ f ≤ 58 Hz
58 Hz ≤ f ≤ 150 Hz
Reducing vibrations
If your S7-300 modules are exposed to severe shock or vibration, take appropriate measures
to reduce acceleration or the amplitude.
We recommend the installation of the S7-300 on damping materials (for example, rubber-
bonded-to-metal mounting.)
RS 485 Repeater
Manual, 02/2011, A5E03382072-01
– the development of dust
– corrosive vapors or gases
– strong electric or magnetic fields
– elevators
– electrical plants in potentially hazardous areas
Continuous
0.0375 mm amplitude
0.5 g constant acceleration
Technical data
6.1 General technical data
Infrequently
0.75 mm amplitude
1 g constant acceleration