Connecting

5.1

RS 485 Repeater in ungrounded and grounded operation

Grounded or ungrounded
The RS 485 repeater is
● Grounded, if all other nodes on the bus segment are also operated on ground potential
● Ungrounded, if all other nodes in the bus segment are operated on ungrounded potential
Grounded operation of the RS 485 Repeater
For grounded operation of the RS 485 repeater, you must bridge terminals "M" and "PE" on
the top of the RS 485 repeater.
Ungrounded operation of the RS 485 repeater
For ungrounded operation of the RS 485 repeater, do not interconnect "M" and "PE" on the
top of the RS 485 repeater. In addition, the supply voltage to the RS 485 repeater must be
ungrounded.
RS 485 Repeater
Manual, 02/2011, A5E03382072-01
Note
Bus segment 1 is referenced to ground if you connect a PG to the PG/OP socket of the
RS 485 repeater. The bus segment is grounded because the MPI in the PG is grounded,
and the PG/OP socket of the RS 485 repeater is connected internally with bus segment
1.