Point Name
Wi-Fi Enable
Setpoint Override
BACnet BMS Occupancy
Filter Timer Reset
Network Space Temp Enable READ_WRITE
Network Space Hum Enable
Occupancy Input Polarity
Auto Mode Allowed
Prog Mode Allowed
Celsius Display
Fan On with W
Rvs Vlv Energized Ht
Humidifier Installed
BMS Occupancy Enable
BACnet Config Write Enable
ID TEMP SENSOR HIGH
ID TEMP SENSOR LOW
REMOTE SENSOR HIGH
REMOTE SENSOR LOW
HUM TEMP SENSOR HIGH
HUM TEMP SENSOR LOW
ID TEMP RANGE HIGH
33CONNECTSTAT43
Installation Guide
Point Access
Units
READ_WRITE
0=DISABLED
1=ENABLED
READ_WRITE
0=DISABLED
1=ENABLED
GATED_WRITE
0=UNOCCUPIED
1=OCCUPIED
READ_WRITE
0=INACTIVE
1=ACTIVE
0=DISABLED
1=ENABLED
READ_WRITE
0=DISABLED
1=ENABLED
GATED_WRITE
0=OCCUPIED
1=UNOCCUPIED
GATED_WRITE
0=NO
1=YES
GATED_WRITE
0=NO
1=YES
GATED_WRITE
0=F°
1=C°
GATED_WRITE
0=NO
1=YES
GATED_WRITE
0=ENERGIZED FOR COOL
1=ENERGIZED FOR HEAT
GATED_WRITE
0=NO
1=YES
GATED_WRITE
0=DISABLED
1=ENABLED
GATED_WRITE
0=DISABLED
1=ENABLED
READ_ONLY
0=DISABLED
1=ENABLED
READ_ONLY
0=INACTIVE
1=ACTIVE
READ_ONLY
0=INACTIVE
1=ACTIVE
READ_ONLY
0=INACTIVE
1=ACTIVE
READ_ONLY
0=INACTIVE
1=ACTIVE
READ_ONLY
0=INACTIVE
1=ACTIVE
READ_ONLY
0=INACTIVE
1=ACTIVE
BACnet Point Name
WIFI_ENABLE
SETPT_OVERRIDE
BMS_OCC
FLTR_TMR_RST
NET_SP_TEMP_EN
NET_SP_HUM_EN
OCC_IN_POL
ALLOW_AUTO
ALLOW_PROG
CELSIUS_DISP
FAN_WITH_W
RVS_VLV_DIR
HUM_INST
BMS_OCC_EN
CFG_WR_EN
ID_TEMP_SENS_HI
ID_TEMP_SENS_LO
REM_TEMP_HI
REM_TEMP_LO
HUM_TEMP_HI
HUM_TEMP_LO
ID_TEMP_RNG_HI
45
Appendix: BACnet Points List
BACnet
Object ID
BV:403
BV:404
BV:405
BV:406
BV:407
BV:408
BV:500
BV:501
BV:502
BV:503
BV:504
BV:505
BV:506
BV:507
BV:511
BV:900
BV:901
BV:902
BV:903
BV:904
BV:905
BV:906
©2022 Carrier.