Installation Guide
VLT® Control Panel LCP
1 Introduction
1.1 Description
This Installation Guide explains how to install the LCP for VLT® HVAC Basic Drive FC 101 and VLT® Flow Drive FC 111.
1.2 Item Supplied
VLT® Control Panel LCP 32 (ordering number: 132B9221).
VLT® Control Panel LCP 31 (ordering number: 132B0200).
1.3 Safety Precautions
Only qualified personnel are allowed to install the LCP described in this Installation Guide.
For important information about safety precautions for installation, refer to the drive's Operating Guide.
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or
serious injury.
-
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
-
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible
on the nameplate on top of the drive.
-
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.
Table 1: Discharge Time for FC 101
Voltage [V]
Power range [kW (hp)]
3x200
0.25–3.7 (0.33–5)
3x200
5.5–11 (7–15)
3x400
0.37–7.5 (0.5–10)
3x400
11–90 (15–125)
3x600
2.2–7.5 (3–10)
3x600
11–90 (15–125)
Table 2: Discharge Time for FC 111
Voltage [V]
Power range [kW (hp)]
3x400
0.37–7.5 (0.5–10)
3x400
11–90 (15–125)
3x400
110–315 (150–450)
Danfoss A/S © 2021.03
W A R N I N G
Minimum waiting time (minutes)
4
15
4
15
4
15
Minimum waiting time (minutes)
4
15
20
AN359636476228en-000201 / 130R0961 | 1

Advertisement

loading

Summary of Contents for Danfoss VLT LCP 32

  • Page 1 2.2–7.5 (3–10) 3x600 11–90 (15–125) Table 2: Discharge Time for FC 111 Voltage [V] Power range [kW (hp)] Minimum waiting time (minutes) 3x400 0.37–7.5 (0.5–10) 3x400 11–90 (15–125) 3x400 110–315 (150–450) Danfoss A/S © 2021.03 AN359636476228en-000201 / 130R0961 | 1...
  • Page 2 Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.