1.1. General Warning 2.1. General Description Please read the following safety precautions and The XR75CX-Case Display (32 mm x 74 mm) is warnings before using this manual: a microprocessor based controller, suitable for appli- cations on medium or low temperature ventilated re- frigeration units.
Case Display Outputs On-Board Relay Outputs The XR75CX-CD has 4 on-board relays that may be used as satellite outputs by other E2 applications. Wire the outputs to the two-wire terminals on the right side of the control unit. For loads greater than 3A, use the outputs to energize external relays.
XR75CX-CD you want to associate. For 4.1. Configuring the example, if you want to associate XR75CX-CD #7 with this circuit, select CL CD007 from the Look-Up Table. XR75CX-CD Through E2...
5.1. Output Relay Control Circuit application in E2, a “Case Temp Hi Limit Exceeded” or “Case Temp Lo Limit Exceeded” The 4 on-board relays on the XR75CX-CD are con- alarm that occurs for the XR75CX-CD’s associated trolled by the associated XR75CX-CD application in case will cause the main module and remote display’s...
Switches the device ON and OFF To enter programming mode Returns to room temperature display Table 6-1 - XR75CX-CD Front Panel Keys and Functions 6 • XR75CX-CD I&O Manual 026-1217 Rev 0 08-NOV-2011...
19200. 6. Press SET to save. NOTE: The set value is stored even when the time-out expires and ends the procedure. The E2 will override values set at the XR75CX Case Display device. 7.2. How to Assign a MODBUS Address 1.
9.1. ON - OFF Function Switches the controller ON and OFF. 9.2. Digital Inputs Polarity Figure 10-1 - Installation and Mounting of XR75CX-CD The digital input polarity depends on the i1P and i2P parameters. The XR75CX-CD controller should be mounted •...
(where most ice is formed) and far from heaters or from the warmest place during defrost to prevent premature defrost termination. 10 • XR75CX-CD I&O Manual 026-1217 Rev 0 08-NOV-2011...
14 Connections Figure 14-1 - XR75CX-CD Connections NOTES: 120V or 230V depending on the model. The Hot Key function is not used on the XR75CX-CD. 12 • XR75CX-CD I&O Manual 026-1217 Rev 0 08-NOV-2011...
18 terminal. • Terminate the end of the MODBUS network at the last XR75CX-CD device on the daisy chain with the MODBUS termination block (P/N 535-2711), or by connecting a 150 ohm resistor between the MODBUS +/- terminals.
Figure 16-1 - Location of E2 Com Ports (E2 versions 3.xx and Below) Connecting a XR75CX-CD controller to an E2 re- quires the E2 to be version 3.02 or above. Contact Re- tail Solutions for upgrade information if the controller Figure 16-2 - Location of E2 COM Ports - E2 PIB Board (E2 is a version before 3.02.
16.3.2.Add and Connect the Device Figure 16-3 - MODBUS Networking To enable communications between E2 and the XR75CX-CD units, the devices must be added and addressed in E2. 16.3. E2 Setup of Devices Log in to the E2 with Level 4 access.
Page 22
. In the list of MODBUS devices, choose the address number corresponding to the XR75CX-CD address set up through the front display, and press to select it. A window will open where you can specify the address of the controller.
Page 23
120W±50W Nominal Impedance 16.5. MODBUS Termination Blocks Because the XR75CX-CD device has no on-board means of termination, use the MODBUS termination block (P/N 535-2711) for termination that can be wired to the end of the cable segment using the three- pin connector.