42 Operation

Energizing and starting the drive

It is recommended to have the following documents at hand when starting the drive
locally for the first time after commissioning:
ACS580MV Wiring Diagram
User's Manual
ACS-AP-X assistant control panels user's manual
[English])

Checks before starting the drive

DANGER
Hazardous voltages!
All covers must be screwed in place to prevent unintentional contact with
energized components.
The manual release of the door safety switches must be in the locked position. The
locked position prevents doors of medium voltage compartments being opened
unintentionally during operation.
When the drive is put into service after it has been commissioned, or after it has
been taken out of service for maintenance or troubleshooting, check the drive
according to the following list:
Check that no tools and foreign objects are left inside the cabinets.
Check that all auxiliary power supplies from external sources are switched on.
Check that all internal circuit breakers of the drive are closed.
Check that all grounding devices are removed
Check that all covers are mounted and the doors are closed, locked and / or
bolted.
Check that the MCB is in operating position.
Check that there is no run interlock active.

Starting the drive from remote

When the drive is operated from remote through a higher-level control system or an
operator control desk, follow the instructions in the appropriate manuals.