11. Safety devices

Type of
protection
Circuit
Current fuse
protection
(Main PCB)
Fan motor
Thermal protection program
protection
Thermal protection program
(Discharge temp.)
Compressor
Thermal protection program
protection
(Compressor temp.)
Thermal protection program
(Outdoor temp.)
Type of
protection
Circuit
Current fuse
protection
(Main PCB)
Fan motor
Thermal protection program
protection
Thermal protection program
(Discharge temp.)
Compressor
Thermal protection program
protection
(Compressor temp.)
Thermal protection program
(Outdoor temp.)
Protection form
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Protection form
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
- 66 -
Model
AOYG36KRTA
250 V, 30 A × 2
250 V, 10 A × 2
122 ±9 °C
Fan motor stop
+10
116
°C
-9
Fan motor restart
110 °C
Compressor stop
After 7 minutes
Compressor restart
108 °C
Compressor stop
80 °C or less
Compressor restart
-20 °C
Compressor stop
-15 °C
Compressor restart
Model
AOYG45KRTA
250 V, 30 A × 2
250 V, 10 A × 2
150 ±15 °C
Fan motor stop
120 ±15°C
Fan motor restart
110 °C
Compressor stop
After 7 minutes
Compressor restart
108 °C
Compressor stop
80 °C or less
Compressor restart
-20 °C
Compressor stop
-15 °C
Compressor restart
11. Safety devices