6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Model: AOYG36KRTA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher
than outdoor unit *1
Indoor unit is lower than
outdoor unit *2
6-1. Model: AOYG36KRTA
Height difference H
1
*
H
Outdoor unit
5
7.5
30
20
10
7.5
0.988
5
0.992
0.992
0
1.000
1.000
-5
1.000
1.000
-7.5
1.000
-10
-20
-30
5
7.5
30
20
10
7.5
1.000
5
1.000
1.000
0
1.000
1.000
-5
0.995
0.995
-7.5
0.993
-10
-20
-30
- 59 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
10
20
30
0.902
0.938
0.917
0.973
0.953
0.933
0.977
0.957
0.936
0.981
0.961
0.940
0.989
0.968
0.947
0.989
0.968
0.947
0.989
0.968
0.947
0.989
0.968
0.947
0.968
0.947
0.947
Pipe length (m)
10
20
30
0.978
0.988
0.978
0.998
0.988
0.978
0.998
0.988
0.978
0.998
0.988
0.978
0.998
0.988
0.978
0.993
0.983
0.973
0.991
0.981
0.971
0.988
0.978
0.968
0.968
0.958
0.949

6. Capacity compensation rate for pipe length and height difference

2
*
40
50
0.882
0.862
0.897
0.876
0.912
0.891
0.916
0.895
0.919
0.898
0.926
0.905
0.926
0.905
0.926
0.905
0.926
0.905
0.926
0.905
0.926
0.905
40
50
0.968
0.958
0.968
0.958
0.968
0.958
0.968
0.958
0.968
0.958
0.968
0.958
0.963
0.953
0.961
0.951
0.958
0.948
0.949
0.939
0.939
0.929