10

Technical data

Further information about the product and accessories is found at:
new.abb.com/low-voltage/products/safety-products
Stated technical data apply when power supply voltage is +24 VDC and ambient temperature
is +25 °C, unless stated otherwise.
Manufacturer
Address
Order code/Ordering data
Power supply
Required power supply type
Operating voltage
Total current consumption
Note: Total current consumption is the internal supply current when there is no
information output current. Valid over the operating voltage and ambient temperature
range.
DYNlink signal
DYNlink Input signal voltage
DYNlink Output signal voltage
Note: The purpose of stating the voltage in RMS is to facilitate the measurement of the
square-wave DYNlink signal with a multimeter.
Time delay between DYNlink
input and output signal (T
Information output
Output voltage high
Output current
General
Protection class
Ambient temperature
2TLC172163M0201 Rev.F
ABB Electrification Sweden AB
SE-721 61 Västerås
Sweden
2TLA030054R0010: INCA 1 Tina v2 Emergency stop
button, red button, 5-pin screw terminal block
2TLA030054R0210: INCA 1S Tina v2 Safety stop
button, black button, 5-pin screw terminal block
2TLA030054R1400: INCA 1EC Tina Emergency stop
button, red button, 5-pin screw terminal block,
StatusBus
PELV/SELV, not intended to be connected to a DC
distribution network.
Note: A DC distribution network is defined in
IEC 61326-3-1:2017 as "Local DC electricity supply
network in the infrastructure of a certain site or
building intended for connection of any type of
equipment".
+24 VDC +15 %, -25 %
Maximum: 35 mA
Minimum: 8 V
Maximum: 15 V
Minimum: 8 V
Maximum: 15 V
Maximum: 70 µs
)
DELAY
Nominal: Operating voltage - 2 VDC
low
Maximum: 2 VDC
Maximum: 10 mA
IP65, connection terminal IP20
Operation: -10 to +55 °C
Storage: -30 to +70 °C
RMS
RMS
RMS
RMS
RMS
15