1. PRODUCT NAME
®
VIKING HORIZON
Model H-3
Residential Flush Pendent Sprinkler
Sprinkler Base Part No: 09458
2. MANUFACTURER
THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058 U.S.A.
Telephone:
(616) 945-9501
(800) 968-9501
Fax Number:
(616) 945-9599
From outside U.S.A.:
Telephone: +1(616) 945-9501
Fax Number: +1(616) 945-9599
3. PRODUCT DESCRIPTION
The Viking Horizon
Model H-3 Resi-
®
dential Sprinkler is a small, flush, high
sensitivity solder link and lever spray
sprinkler. The sprinkler is available in
several finishes with temperature ratings
to meet varying design requirements.
The sprinkler is listed for use in resi-
dential applications below smooth,
flat horizontal ceilings with spacings
up to 20' x 20' and ceilings with
slopes up to and including a 6/12
o
pitch (26.6
) with spacings up to 18' x
18'. Designed for use with concealed
piping, the unit is mounted flush with the
ceiling, with the fusible link exposed.
The separate decorative ceiling ring al-
lows for up to 1/2" (12,7 mm) adjustment.
The two piece design allows the instal-
lation and testing of the sprinklers prior
to the installation of the ceiling. The ceil-
ing ring can be removed and re-installed
allowing access above removable ceil-
ing panels without shutting down the
sprinkler system and removing the sprin-
kler. The deflector is held inside the body
until the eutectic metal solder link is
fused. During fire conditions, when the
fusible link reaches its operating tem-
perature, the link, levers and center
Form No. 062395
R
TECHNICAL DATA
cover plate fall away. The deflector is
suspended below the ceiling.
flowing through the sprinkler orifice
strikes the deflector forming a uniform
spray pattern over a specific area of
coverage determined by the water sup-
ply pressure at the sprinkler.
4. TECHNICAL DATA
See chart below for listings.
Rated to 175 PSI (1 207 kPa) water
working pressure.
Factory tested pneumatically to 95 PSI
(655 kPa).
See Chart for minimum water supply
Sprinkler
Temperature
Classification
Ordinary
Intermediate
Deflector
Thread Size
Style
Size NPT
Inch
mm
Pendent
1/2
15
AREA OF COVERAGE
Maximum
3
Coverage
Single Sprinkler
20' x 20'
19 GPM @ 25 PSI
5
6.1M x 6.1M
72 L/Min @ 173 kPa
5
18' x 18'
16 GPM @ 17.7 PSI
5.5M x 5.5M
61 L/Min @ 122 kPa
5
13 GPM @ 11.7 PSI
16' x 16'
4.9M x 4.9M
50 L/Min @ 122 kPa
5
14' x 14'
11 GPM @ 8.4 PSI
4.3M x 4.3M
42 L/Min @ 58 kPa
5
12' x 12'
10 GPM @ 7.0 PSI
3.7M x 3.7M
38 L/Min @ 48 kPa
6
16' x 16' (sloped)
16 GPM
4.9M x 4.9M
61 L/Min @ 122 kPa
6
18' x 18' (sloped)
20 GPM
5.5M x 5.5M
76 L/Min @ 191 kPa
Temperature Rating
A: 165 o F (74 o C)
1
Metric K Factor shown is for use use when pressure is measured in kPa. When pressure is measured
in BAR, multiply the metric K Factor shown by 10.0.
2
Base part number shown. For complete part number, see Price List.
3
For areas of coverage smaller than those shown, use the "Minimum Water Supply Requirement" for the
next larger "Area of Coverage" listed for the sprinkler used. The distance from sprinklers to walls shall
not exceed one half the sprinkler spacing indicated for the "Minimum Water Supply Requirement" used.
4
This chart shows the listings and approvals available at the time of printing. Other approvals are in
process. Check with manufacturer for any additional approvals.
5
Listing is for Residential occupancies with smooth, flat horizontal ceilings.
6
Listing is for all Residential occupancies with ceilings sloped between a 0/12 pitch (0
o
pitch (26.6
). Areas under sloped ceilings must be measured along the slope. Refer to Figure C
Installation Notes, on page 145 d.
7
Listed by Underwriters Laboratories, Inc. for use in Canada.
8
Acceptance by City of New York Department of Buildings is pending.
HORIZON
RESIDENTIAL PENDENT
SPRINKLER 3.8 K-FACTOR
requirements and maximum area of
Water
coverage.
Spring: USA Patent No. 4,570,720
Requires a 2" (50,8 mm) diameter hole
in ceiling.
See chart below for temperature ratings.
Thread Size: Nominal 1/2" (15mm) NPT
K Factor: 3.8 (5,5 metric*)
*
Metric K Factor shown is for use when pressure
is measured in kPa. When pressure is meas-
ured in BAR, multiply the metric K Factor shown
by 10.0.
Finishes:
Bright Brass, Polished Chrome,
White (Paint), and Navajo White (Paint)
Highest Normal
Nominal
Ambient Temp.
Temperature
Allowed
Rating
o
o
o
165
F (68
C)
100
o
o
o
220
F (104
C)
150
Nominal
Overall
K Factor
Length
1
US
Metric
Inch
mm
3.8
5,5
2-5/8
66,7
4
Minimum Water Supply Requirements
Two or More
17 GPM @ 20 PSI
65 L/Min @ 138 kPa
13 GPM
@ 11.7 PSI
50 L/Min @ 81 kPa
11 GPM @ 8.4 PSI
42 L/Min @ 58 kPa
10 GPM @ 7.0 PSI
38 L/Min @ 48 kPa
10 GPM @ 7.0 PSI
38 L/Min @ 48 kPa
@ 17.7 PSI
12 GPM @ 9.9 PSI
45 L/Min @ 68 kPa
@ 27.7 PSI
17 GPM @ 20.0 PSI
64 L/Min @ 138 kPa
1: Polished Chrome, Bright Brass,
White (paint), Navajo White (paint)
Footnotes
Replaces page 145a-d dated October 23, 1996
(Revised Sloped Ceiling Listings)
Sprinkler 145 a
®
MODEL H-3
Temperature
Identification
Stamp
o
F (46
C)
On Cover
o
F (66
C)
On Cover
Base
2
Part Number
09458
APPROVAL KEY
Temperature
A 1
Finish
5,6
7
8
UL
C-UL
NYC
A1
A1
--
A1
A1
--
A1
A1
--
A1
A1
--
A1
A1
--
A1
A1
--
--
A1
A1
Finishes
o
) and a 6/12
--

Advertisement

loading

Summary of Contents for Viking HORIZON H-3

  • Page 1 Sprinkler Base Part No: 09458 Intermediate F (104 F (66 On Cover 2. MANUFACTURER Deflector Thread Size Nominal Overall Base THE VIKING CORPORATION Style Size NPT K Factor Length Part Number 210 N. Industrial Park Road Inch Metric Inch Hastings, Michigan 49058 U.S.A.
  • Page 2 6. GUARANTEES place in their original shipping con- Sprinkler For details of warranty, refer to Viking’s tainer. Never install sprinklers that Wrench** current list price schedule or contact Vi- have been dropped, damaged in any Part No.
  • Page 3 June 9, 1997 Sprinkler 145 c ® HORIZON MODEL H-3 TECHNICAL DATA RESIDENTIAL PENDENT SPRINKLER 3.8 K-FACTOR Figure B the recognized installation stand- Having Jurisdiction. Consideration 8. MAINTENANCE ards. The test is applied after the should be given to employment of a NOTICE: The owner is responsible for sprinkler installation to ensure no fire patrol in the affected area.
  • Page 4 Sprinkler 145 d June 9, 1997 ® HORIZON MODEL H-3 TECHNICAL DATA RESIDENTIAL PENDENT SPRINKLER 3.8 K-FACTOR Listed Areas of Coverage correspond to areas measured along ceiling slope. (for sloped ceiling installations, Maximum actual floor coverage will be ceiling less than listed area). slope = 6/12.