Hach si792 T Series User Manual

Inductive conductivity 2-wire transmitter
Hide thumbs Also See for si792 T Series:
Table of Contents

Advertisement

Quick Links

DOC026.52.00796
si792(x) E—Hach GLI 3700 series
si792(x) T—7MA2200 and 8398 series
Inductive Conductivity
2-Wire Transmitter
USER MANUAL
December 2007, Edition 1
© HACH Company, 2007. All rights reserved. Printed in Germany

Advertisement

Table of Contents
loading

Summary of Contents for Hach si792 T Series

  • Page 1 DOC026.52.00796 si792(x) E—Hach GLI 3700 series si792(x) T—7MA2200 and 8398 series Inductive Conductivity 2-Wire Transmitter USER MANUAL December 2007, Edition 1 © HACH Company, 2007. All rights reserved. Printed in Germany...
  • Page 3: Table Of Contents

    3.5.2.2 si792x E/T-FF and si792x E/T-PA wiring ....25 3.5.3 Sensor wire connections ........... 25 3.5.3.1 Hach GLI 3700 series sensor wiring—si792(x) E ..26 3.5.3.2 7MA2200 series sensor wiring—si792(x) T ....27 3.5.3.3 8398 series sensor wiring—si792(x) T....... 28...
  • Page 4 Table of Contents Section 4 Interface and navigation ........31 4.1 si792(x) E/T (4–20 mA/HART) interface........31 4.2 si792x E/T-FF and si792x E/T-PA interface ......32 4.3 Display..................33 Section 5 Operation—4–20 mA/HART ......35 5.1 Measure mode ................. 35 5.2 Configuration ................
  • Page 5 Table of Contents 7.1.2 Configuration menu............66 7.2 Profibus PA communication ............. 67 Section 8 Calibration .............. 71 8.1 Calibration ................71 8.1.1 Enter cell constant............. 72 8.1.2 Calibration with a calibration solution ........ 73 8.1.3 Calibration by comparison/grab sample ......74 8.1.4 Zero calibration—air............
  • Page 6 Table of Contents B.6 Nitric acid -05- HNO ............. 103 Appendix C Passcode editor ..........105 Appendix D ATEX safety instructions ......107 Index ....................111...
  • Page 7: Section 1 Specifications

    Section 1 Specifications Specifications are subject to change without notice. Transmitter Composition PBT (polybutylene terephthalate) Display 3 knockouts for M20 x 1.5 strain reliefs Fittings 2 knockouts for ½ inch NPT or rigid metallic conduit Power requirements—HART 14–30 VDC (30 VDC maximum) Power requirements—FF and Profibus FISCO bus supply: 9 to 17.5 VDC Linear barrier: 9 to 24 VDC...
  • Page 8 Specifications si792 E/T FM Listed for: Class I, Division 2 si792x E/T; si792x E/T-FF; si792x E/T-PA FM Listed for: Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F Class III, Division 1 Class I, Zone 0, AEx ia, Group IIC T4 Enclosure: Type 2 Canada: si792 E/T...
  • Page 9 Specifications Parameters and calibration data Data retention > 10 years (EEPROM) Modifiable according to FDA 21 CFR Passcodes Part 11 “Electronic Signatures” (HART only) Monitoring of primary coil and its lines Sensocheck for short circuit and of secondary and its lines for open circuit Direct display of measured values from Sensor monitor sensor for validation (resistance/...
  • Page 10 Connection: via segment coupler to SPC, PC, PCS Address range: 1 to 126 Conductivity input 7MA2200 series 8398 series Hach 3700 series Electrodeless conductivity sensors, ranges Conductivity 0.00–1999 mS/cm Concentration 0–100% by weight Salinity 0.0–45 ‰ (0–35 °C) 0.000–9.999 mS/cm 00.00–99.99 mS/cm...
  • Page 11 Specifications Range, Pt100/Pt1000 –20.0 to 200.0 °C (–4 to 392 °F) Range, NTC 30 kΩ –20.0 to 150.0 °C (–4 to 302 °F) Range, NTC 100 kΩ –20.0 to 130.0 °C (–4 to 266 °F) Adjustment range 10 K Resolution 0.1 °C;...
  • Page 12 Specifications...
  • Page 13: Section 2 General Information

    Section 2 General information 2.1 Safety information Please read this entire manual before unpacking, setting up, or operating this equipment. Pay attention to all danger and caution statements. Failure to do so could result in serious injury to the operator or damage to the equipment.
  • Page 14 General information Electrical equipment marked with this symbol may not be disposed of in European public disposal systems after 12 August of 2005. In conformity with European local and national regulations (EU Directive 2002/96/EC), European electrical equipment users must now return old or end-of life equipment to the Producer for disposal at no charge to the user.
  • Page 15: General Product Information

    General information 2.2 General product information DANGER Explosion hazard. The Hach GLI 3700 series sensors can only be used with the si792(x) E transmitter. 2.2.1 Product overview The si792 T, si792x T, si792 E and si792x E transmitters are used for measurement of electrical conductivity and temperature in liquids.
  • Page 16: Fda 21 Cfr Part 11 Compliance (Hart Only)

    General information 2.2.2 FDA 21 CFR part 11 compliance (HART only) In the directive “Title 21 Code of Federal Regulations, 21 CFR Part 11, Electronic Records; Electronic Signatures“ the US American health agency FDA (Food and Drug Administration) regulates the production and processing of electronic documents for pharmaceutical development and production.
  • Page 17: Section 3 Installation

    Section 3 Installation DANGER Explosion hazard. Trained personnel only must install or commission the equipment. DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous.
  • Page 18: Hazardous Location Installation

    Installation 3.1 Hazardous location installation Before installation, review the applicable Hazardous Location Control Drawings or ATEX EC-Type Examination certificate and safety information included with the instrument and on the provided documentation CD. Follow all regulations specified for the installation location. Refer to the documentation CD for manuals provided in other languages.
  • Page 19: Unpacking The Transmitter

    Installation 3.2 Unpacking the transmitter Check the shipment for transport damage and make sure all components have been shipped complete. The package includes: • Display module • Bag of hardware and fasteners • Back enclosure • Test report and user manual Figure 1 Instrument Components 1 Back enclosure 8 Strain relief (3x)
  • Page 20: Mechanical Installation

    Installation 3.3 Mechanical installation 3.3.1 Transmitter assembly Refer to Figure 1 and the following instructions to assemble the transmitter. 1. Insert the strain relief fittings in the holes of the back enclosure and secure with the hex nuts (Figure 2. Insert the conduit hardware or plugs in the back enclosure and secure with the hex nuts.
  • Page 21 Installation Figure 2 Wall attachment dimensions 1 Breakout for wall mounting (2x) 5 Groove for panel mount gasket 2 Hole for pipe mounting (4x) 6 Strain relief opening (3x) 3 Strain relief (3x) 7 Strain relief or ½ inch conduit opening (2x) Ø...
  • Page 22: Wiring Safety Information

    Installation 3.4 Wiring Safety Information When making any wiring connections to the instrument, the following warnings and notes must be adhered to, as well as any warnings and notes found throughout the individual installation sections. For more safety information refer to section 2.1 on page DANGER Always disconnect power to the instrument when making any...
  • Page 23: Electrical Installation

    Installation Electrical installation DANGER Explosion hazard. Do not connect any components that are not specified for the device. Always defer to the Hazardous Location Control Drawing. Prerequisites: • Review the applicable control drawing or ATEX EC-Type Examination certificate • Review the electrical code regulations •...
  • Page 24 Installation Figure 3 Wire preparation and insertion 1 Stripping lengths for cables 6 Terminals (vary by model number) 2 Stripping lengths for coaxial cables 7 Typical terminal 3 Cable shield connector (not used) 8 Seat insulation against connector 4 ESD shield removed 9 Removing terminal with screwdriver 5 Areas for screwdriver to pry terminal 10 Cable loop position in housing...
  • Page 25: Power And Communication Connections

    Installation 3.5.2 Power and communication connections DANGER Explosion hazard. The AC power source for the power supply unit cannot exceed 250 VAC. Do not connect the transmitter directly to an AC power source. DANGER Explosion hazard. The output voltage of the power supply unit cannot exceed 30 VDC.
  • Page 26: Si792(X) E/T (4-20 Ma/Hart) Wiring

    Installation 3.5.2.1 si792(x) E/T (4-20 mA/HART) wiring DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing/ATEX EC-Type certificate. Refer to Figure 4 Table 1 to connect the power supply to the si792(x) E/T transmitter. Figure 4 si792(x) E/T (4–20 mA/HART) wiring 1 HART connection (see warnings in 2 Wiring terminals—see...
  • Page 27: Si792X E/T-Ff And Si792X E/T-Pa Wiring

    Important Note: Do not connect earth ground to the shield connector in the transmitter. Connect the cable shields to the shield connector. Refer to the following sections to connect the transmitter to a sensor: • Hach GLI 3700 series—section 3.5.3.1 on page 26 • 7MA2200...
  • Page 28: Hach Gli 3700 Series Sensor Wiring-Si792(X) E

    Figure 2. Use Table 3 to wire the sensor to the transmitter. Figure 6 si792(x) E wiring for Hach GLI 3700 series sensors 1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 3 Table 3 Terminal assignments—Hach GLI 3700 series sensors Terminal No.
  • Page 29: 7Ma2200 Series Sensor Wiring-Si792(X) T

    Installation 3.5.3.2 7MA2200 series sensor wiring—si792(x) T 1. Install the jumper between terminal 2 and 3 as shown in Figure 2. Use Table 4 to wire the sensor to the transmitter. Figure 7 si792(x) T wiring for 7MA2200 series sensors 1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 4...
  • Page 30: 8398 Series Sensor Wiring-Si792(X) T

    Installation 3.5.3.3 8398 series sensor wiring—si792(x) T 1. Install the jumper between terminal 2 and 3 as shown in Figure 2. Use Table 5 to wire the sensor to the transmitter. Figure 8 si792(x) T wiring for 8398 series sensors 1 Jumper between terminal 2 and 3 2 Wiring terminals—see Table 5...
  • Page 31: Hart Communication Connection

    Installation 3.6 HART communication connection DANGER Explosion hazard. Never connect items to the transmitter that are not specified on the control drawing. Do not connect or disconnect any equipment unless power has been switched off or the area is known to be non-hazardous. DANGER The si792x transmitter must be used with an explosion-proof HART communication device.
  • Page 32 Installation...
  • Page 33: Section 4 Interface And Navigation

    Section 4 Interface and navigation The si792 transmitter user interface contains a display, indicators and keys for navigation and menu selection. 4.1 si792(x) E/T (4–20 mA/HART) interface Use the arrow and enter keys to scroll through the menu and change settings.
  • Page 34: Si792X E/T-Ff And Si792X E/T-Pa Interface

    Interface and navigation 4.2 si792x E/T-FF and si792x E/T-PA interface Refer to Figure 10 to identify the keys and indicators of the si792x E/T-FF and si792x E/T-PA transmitter. Figure 10 User interface—si792x E/T-FF and si792x E/T-PA 1 Measure key 7 Communication indicator 2 Calibration key 8 Configuration mode indicator 3 Measure mode indicator...
  • Page 35: Display

    Interface and navigation 4.3 Display Figure 11 identifies all of the possible icons and symbols that may be seen in the si792 transmitter display. Figure 11 Display 1 Passcode 13 Secondary display 2 Temperature 14 Alarm mode 3 4–20 mA output 15 Manual temperature on 4 Limit values (FF and Profibus PA) 16 Calibration mode...
  • Page 36 Interface and navigation...
  • Page 37: Section 5 Operation-4-20 Ma/Hart

    Section 5 Operation—4–20 mA/HART The following section describes how to operate the si792(x) E/T transmitter. 5.1 Measure mode The display shows the configured process variable (conductivity, concentration, resistivity or salinity) and the temperature value in the measuring mode. • To return to the measurement mode during calibration press ENTER •...
  • Page 38: Current Output Configuration

    0.100–20.000 (3.00 default—si792 T; 4.70 default—si792 E) Enter the transfer ratio o1.SFC 1.00–200.00 (68.0 default—si792 T; 25.0 default—si792 E) Select the temperature sensor Pt100 (default—si792 T) Pt1000 (default—si792 E for GLI/Hach 3700 series sensors) o1.rTD NTC100 NTC30 Select the range and units 0.000 mS/cm (si792 T) 00.00 mS/cm...
  • Page 39 Operation—4–20 mA/HART 5.2.1 Current output configuration (continued) If range is set to 000.0% select solution (Conc) -01- NaCl (default) -02- HCI -03- NaOH -04- H Solution (Conc) -05- HNO o1.ConC (refer to section B.1 on page 97 for more -06- H information) -07- HCI -08- HNO...
  • Page 40 Operation—4–20 mA/HART 5.2.1 Current output configuration (continued) Specify the value to output during HOLD periods During HOLD the entered value is o1.FIX 21.0 mA (default) maintained at the output (refer to section 5.2.1.3 for more information) If “Other” sensor is selected, o1.CELL, o1.SFC and o1.rTD are available If the process variables SAL, % (Conc) or USP are selected the following steps (Lin/Log) are omitted.
  • Page 41: Time Constant Of Output Filter

    Operation—4–20 mA/HART 6. Press to exit the configuration menu. CONF ENTER The transmitter remains in HoLD mode for approximately 20 seconds after calibration and returns to the measurement mode. 5.2.1.1 Time constant of output filter An averaging filter is available to reduce noise in the output signal. The filter averages readings over a specified time interval.
  • Page 42: Output Signal During Hold

    Operation—4–20 mA/HART 5.2.1.3 Output signal during HOLD The output signal during hold periods can be maintained at the last measured value (Figure 12) or fixed at a specified value (Figure 13). The allowable range for the fixed value is 3.4 to 22 mA. Figure 12 Output signal during HOLD—last value 1 Output signal during HOLD 2 HOLD mode...
  • Page 43: Temperature Compensation Configuration

    Operation—4–20 mA/HART 5.2.2 Temperature compensation configuration Select temperature unit °C (default) tc.UnIT °F Select temperature compensation Linear temperature compensation with entry of temperature coefficient. Reference temperature = 25 °C Lin (default) Enter temperature coefficient tc. LIN 02.00%/K (default) (xx.xx%/K) Temperature compensation for naturals waters to EN 27888 Temperature compensation turned off If SAL or USP is selected, the following steps are omitted.
  • Page 44: Alarm Settings

    Operation—4–20 mA/HART 5.2.3 Alarm settings Select Sensocheck CHECK ON Continuous Sensocheck evaluation of AL.SnSO sensor function CHECK OFF (default) Enter alarm delay AL.dLY 0010 sec (default) Range: 0–600 sec LED in Hold mode HOLD ON LED blinks during hold AL.LED HOLD OFF LED off during hold...
  • Page 45: Section 6 Operation-Foundation Fieldbus

    Section 6 Operation—Foundation Fieldbus The following section describes how to navigate and operate the si792x E/T-FF transmitter. The transmitter can be operated as follows: • Direct interface with the transmitter (section 6.1) • Foundation Fieldbus communication (section 6.2 on page 6.1 Configuration Use the configuration mode to specify the sensor, range and other parameters for the system.
  • Page 46: Configuration Menu

    Operation—Foundation Fieldbus 6.1.2 Configuration menu Select the sensor 2208 SIE (7MA2200 series; default) si792 T: 8398 PM In.SnSR Other 3700 GLI (default) si792 E: Other Select nominal cell factor (other sensor) ln.CELL 00.100 – 20.000 (default: 1.980) Select the transfer ratio (other sensor) ln.SFC 0010.00 –...
  • Page 47 Operation—Foundation Fieldbus 6.1.2 Configuration menu (continued) Select the variable/unit 0.000 mS/cm 00.00 mS/cm 000.0 mS/cm (default) 0.000 S/m 00.00 S/m 00.00 SAL -01- NaCl (default) -02- HCl ln.UnIT -03- NaOH -04- H -05- HNO 000.0% ln.CoNC -06- H -07- HCl -08- HNO -09- H -10- NaOH...
  • Page 48 Operation—Foundation Fieldbus 6.1.2 Configuration menu (continued) LED in Hold mode HOLD ON LED blinks during hold AL.LED HOLD OFF (default) LED off during hold Enter Fieldbus address (optional) FF.ADR 0017 – 0031 BUS (default: 0026 BUS) Use only when there is no bus connection. The transmitter will restart and set all parameters to default values.
  • Page 49: Foundation Fieldbus Communication

    Target Actual MODE_BLK Permitted OOS, Auto Normal Auto BLOCK_ERR Block error RS_STATE Resource state TEST_RW Test DD_RESOURCE DD resource MANUFAC_ID Manufacturer ID 0x001D6D for Hach si792 T: 0068 DEV_TYPE Device type si792 E: 0066 DEV_REV Device revision DD_REV DD revision...
  • Page 50 Operation—Foundation Fieldbus Table 7 Bus parameters—resource block (RB) (continued) Parameter Description Default Grant GRANT_DENY Deny HARD_TYPES Hardware type RESTART Restart FEATURES Feature supported Reports/ Soft W Lock FEATURES Feature selected Reports/ Soft W Lock Scheduled/ CYCLE_TYPE Cycle type Block Execution Scheduled/ CYCLES_SEL Cycle selected...
  • Page 51 Operation—Foundation Fieldbus Table 7 Bus parameters—resource block (RB) (continued) Parameter Description Default Unacknowledged Alarm state BLOCK_ALM Time stamp Sub-code Value Current Unacknowledged ALARM_SUM Unreported Disabled Automatic acknowledge ACK_OPTION 0 (disabled) option WRITE_PRI Write priority Unacknowledged Alarm state WRITE_ALM Time stamp Sub-code Value ITK_VER...
  • Page 52: Standard Analog Input Block (Ai)

    Operation—Foundation Fieldbus 6.2.2 Standard analog input block (AI) Three Analog Input Function Blocks provide for cyclic transmission of measured values (currently measured value with status, alarm limits, freely selectable process parameter). 6.2.2.1 Operating modes Use the MODE_BLK parameter to set the following operating modes: •...
  • Page 53: Data Processing

    Operation—Foundation Fieldbus 6.2.2.3 Data processing Use the L_TYPE parameter to apply a linearization function to the data. • Direct—data is sent directly from the TB to the AI without processing. The units for the XD_SCALE and OUT_SCALE parameters must be identical. •...
  • Page 54: Bus Parameters For The Analog Input Block

    Operation—Foundation Fieldbus 6.2.2.5 Bus parameters for the analog input block The bus parameters for the analog input function block (AI) are shown Table Table 9 Bus parameters/analog input blocks (AI) Parameter Description Default ST_REV Static Revision TAG_DESC TAG Description STRATEGY Strategy ALERT_KEY Alert Key...
  • Page 55 Operation—Foundation Fieldbus Table 9 Bus parameters/analog input blocks (AI) (continued) Parameter Description Default Grant GRANT_DENY Deny IO_OPTS IO Block Options STATUS_OPTS Status Options CHANNEL Channel L_TYPE Linearization Type LOW_CUT Low Cut Off PV_TIME Filter Time Percent Value FIELD_VAL Status Unacknowledged Update State UPDATE_EVT Time Stamp...
  • Page 56 Operation—Foundation Fieldbus Table 9 Bus parameters/analog input blocks (AI) (continued) Parameter Description Default LO_LIM Low Limit –INF LO_LO_PRI Low Low Priority LO_LO_LIM Low Low Limit –INF Unacknowledged Alarm State HI_HI_ALM Time Stamp Sub-code Value Unacknowledged Alarm State HI_ALM Time Stamp Sub-code Value Unacknowledged...
  • Page 57: Cyclic Measured Value Status

    Operation—Foundation Fieldbus 6.2.2.6 Cyclic measured value status The cyclic measured value status is shown in Table Table 10 Cyclic measured value status Bin-coding Hex- Priority Quality Sub-status (no limit bits) coding Good Non-Specific 10 00 00 00 0 x 80 Good Good Active Advisory Alarm 10 00 10 xx...
  • Page 58: Transducer Block

    Operation—Foundation Fieldbus...
  • Page 59 Operation—Foundation Fieldbus...
  • Page 60 Operation—Foundation Fieldbus...
  • Page 61 Operation—Foundation Fieldbus...
  • Page 62 Operation—Foundation Fieldbus...
  • Page 63 Operation—Foundation Fieldbus...
  • Page 64 Operation—Foundation Fieldbus...
  • Page 65: Calibration Via Foundation Fieldbus

    Operation—Foundation Fieldbus 6.2.4 Calibration via Foundation Fieldbus The transmitter can be calibrated via Foundation Fieldbus using the comparison or grab sample method. 1. Make sure the system is configured for conductivity (PRIMARY_VALUE_TYPE = mS/cm or S/m). 2. Collect a grab sample and set CAL_SAMPLE_PRD to sample. The conductivity value of the sample is stored.
  • Page 66 Operation—Foundation Fieldbus...
  • Page 67: Section 7 Operation-Profibus Pa

    Section 7 Operation—Profibus PA The following section describes how to navigate and operate the si792x Profibus-PA transmitter. The transmitter can be operated as follows: • direct interface with the transmitter (section 7.1) • remote operation from the control station (section 7.2 on page Note: Calibration must be completed by direct interface with the transmitter.
  • Page 68: Configuration Menu

    Operation—Profibus PA 7.1.2 Configuration menu Select the range and units 0.000 mS 00.00 mS 000.0 mS (default) 0000 mS -01- NaCl (default) -02- HCl -03- NaOH 000.0% -04- H (0 – 35% by weight) -05- HNO -06- H (95 – 99% by weight) 000.0 SAL Select temperature unit °C (default)
  • Page 69: Profibus Pa Communication

    Operation—Profibus PA 7.1.2 Configuration menu (continued) Select Sensocheck CHECK ON Continuous Sensocheck evaluation of sensor function CHECK OFF (default) Enter Profibus address Edit 0001–0126 BUS (default: 0126) Temperature compensation is not available for salinity. Use only when there is no bus connection. The transmitter will restart and set all parameters to default values.
  • Page 70 Operation—Profibus PA...
  • Page 71 Operation—Profibus PA...
  • Page 72 Operation—Profibus PA...
  • Page 73: Section 8 Calibration

    Section 8 Calibration 8.1 Calibration Important Note: Use a thermometer to make sure that the displayed temperature is accurate. Important Note: Enter the sensor data in the configuration menu before calibration. Important Note: The transmitter must be calibrated each time a new sensor is connected.
  • Page 74: Enter Cell Constant

    Calibration o1.HoLD menu option. The Sensoface icon is inactive. The calibration mode indicator is displayed (Figure 11 on page 33). To exit the calibration mode at any time, press and then ENTER The output current will be held for 20 seconds and the measured value will be displayed.
  • Page 75: Calibration With A Calibration Solution

    Calibration 8.1.2 Calibration with a calibration solution Use a calibration solution with a known conductivity value to adjust the transmitter to show the same value as the solution. Note: Stabilize the temperature during calibration. 1. Press , enter passcode: 0110, .
  • Page 76: Calibration By Comparison/Grab Sample

    Calibration 8.1.3 Calibration by comparison/grab sample The sensor can be calibrated by measuring the process water with a portable instrument or taking a grab sample and measuring its value in the lab (one-point calibration). The sensor does not need to be removed from the process during calibration.
  • Page 77: Zero Calibration-Air

    Calibration 8.1.4 Zero calibration—air 1. Press , enter passcode: 1001, . CAL ZRO will be ENTER displayed for 3 seconds. 2. Remove and clean the sensor. Note: Make sure that the sensor is dry. 3. Use the to change the value until UP ARROW RIGHT ARROW zero is displayed as the conductivity value.
  • Page 78: Temperature Sensor Adjustment

    Calibration Note: If the entry of the zero point value takes longer than 6 seconds, the display will alternate between showing the conductivity value and the temperature value. 5. Press to confirm. ENTER 6. The display will show the new cell constant value and the zero point.
  • Page 79: Section 9 Maintenance

    Section 9 Maintenance DANGER Explosion hazard. Only qualified personnel should conduct the tasks described in this section of the manual. DANGER Electrostatic hazard. Follow the instructions in Electrostatic Discharge (ESD) Considerations on page 20 before conducting any maintenance tasks. 9.1 Cleaning the instrument Use only a moistened antistatic, lint-free cloth to remove dust, dirt and spots from the external surfaces of the transmitter.
  • Page 80 Maintenance...
  • Page 81: Section 10 Troubleshooting

    Section 10 Troubleshooting 10.1 Sensoface The Sensoface feature is active whenever Sensocheck is active. This feature monitors the sensor for defects in the sensor or cable, and indicates the maintenance status of the sensor (see Table 15). Table 15 Sensoface description Sensoface Description The sensor is operating properly.
  • Page 82: Error Codes

    Troubleshooting Table 16 Error descriptions Display Problem Description Test the primary (send) coil Sensor is Test the secondary (receive) coil defective Refer also to Err 33 and Err 34 (Table 17). Make sure that the measured temperature is within Temperature the range of the temperature compensation table error (temperature compensation, concentration,...
  • Page 83 Corrective action Test the temperature sensor wiring. Make sure that the correct temperature sensor was selected in the configuration menu (GLI/Hach 3700 series sensors use Pt1000). Temperature sensor icon Measure the resistance of ERR 03 flashes; open or short circuit;...
  • Page 84: Diagnostic Tests

    Troubleshooting Table 17 Error codes (continued) Code Description Corrective action ERR 34 Sensocheck icon flashes; Test the secondary (receive) Sensoface icon active (see coil section 10.2) CONF flashes; configuration or calibration data is Reconfigure and calibrate ERR 98 defective. Memory error in the device.
  • Page 85 Troubleshooting 10.4 Diagnostic tests (continued) Function Description From the measuring mode, press and enter passcode CONF ‘5555’. The measured current will show in the secondary display. The output current in the main display can be modified. To change the output current: 1.
  • Page 86 Troubleshooting...
  • Page 87: Section 11 Replacement Parts

    Section 11 Replacement parts 11.1 si792 transmitter versions Description Catalog number si792(x) E versions (for Hach GLI 3700 series) si792 E, inductive conductivity, CID2 LXV503.99.70002 si792x E, inductive conductivity, CID1; ATEX Zone 1 LXV503.99.70102 si792x E-PA, inductive conductivity, CID1; ATEX Zone 1 LXV503.99.76102...
  • Page 88 Replacement parts...
  • Page 89: Section 12 Contact Information

    HACH Company World Repair Service in the Repair Service in Headquarters United States: Canada: P.O. Box 389 HACH Company Hach Sales & Service Loveland, Colorado Ames Service Canada Ltd. 80539-0389 U.S.A. 100 Dayton Avenue 1313 Border Street, Unit 34 Tel (800) 227-HACH...
  • Page 90 Contact information HACH LANGE FRANCE HACH LANGE SA DR. LANGE NEDERLAND S.A.S. B.V. Motstraat 54 33, Rue du Ballon B-2800 Mechelen Laan van Westroijen 2a F-93165 Noisy Le Grand Tél. +32 (0)15 42 35 00 NL-4003 AZ Tiel Tél. +33 (0)1 48 15 68 70 Fax +32 (0)15 41 61 20 Tel.
  • Page 91 Contact information HACH LANGE HACH LANGE SU HACH LANGE D.O.O. ANALİZ SİSTEMLERİ 8, Kr. Sarafov str. Fajfarjeva 15 LTD.ŞTİ. BG-1164 Sofia SI-1230 Domžale Tel. +359 (0)2 963 44 54 Hilal Mah. 75. Sokak Tel. +386 (0)59 051 000 Fax +359 (0)2 866 04 47...
  • Page 92: Section 13 Limited Warranty

    Section 13 Warranty, liability and complaints The manufacturer warrants that the product supplied is free of material and manufacturing defects and undertakes the obligation to repair or replace any defective parts at zero cost. The warranty period for instruments is 24 months. If a service contract is taken out within 6 months of purchase, the warranty period is extended to 60 months.
  • Page 93 Warranty, liability and complaints To avoid or limit consequential damage, it is therefore recommended to design the control loop such that a malfunction in an instrument results in an automatic change over to the backup control system; this is the safest operating state for the environment and the process.
  • Page 94 Warranty, liability and complaints...
  • Page 95: Appendix A Calibration Solutions

    Appendix A Calibration solutions Note: Use the tables in this section to calibrate the transmitter when automatic temperature compensation is set to off. Table 18 Potassium Chloride solutions (Conductivity in mS/cm) Temperature Concentration °C °F 0.01 mol/L 0.1 mol/L 1 mol/L 0.776 7.15 65.41...
  • Page 96 Calibration solutions 1Data source: K. H. Hellwege (Editor), H. Landolt, R. Börnstein: Zahlenwerte und Funktionen ..., volume 2, part. volume 6 Table 19 Sodium Chloride solutions (Conductivity in mS/cm) Temperature Concentration °C °F 0.01 mol/L 0.1 mol/L Saturated 0.631 5.786 134.5 33.8 0.651...
  • Page 97 Calibration solutions Table 19 Sodium Chloride solutions (Conductivity in mS/cm) Temperature Concentration °C °F 0.01 mol/L 0.1 mol/L Saturated 78.8 1.207 10.898 256.5 80.6 1.232 11.114 261.6 82.4 1.256 11.332 266.9 84.2 1.281 11.552 272.1 1.306 11.773 277.4 87.8 1.331 11.995 282.7 89.6...
  • Page 98 Calibration solutions...
  • Page 99: Appendix B Concentration Curves

    Appendix B Concentration curves B.1 Concentration measurement ranges For the solutions listed in Table 20, the transmitter determines the concentration from the measured conductivity and temperature values in % by weight. The measurement error is made up of the sum of measurement and the stored accuracy of the concentration curves.
  • Page 100 Concentration curves Table 20 Concentration ranges Substance Solution Range (% by weight) Temperature 0–26% 0 °C NaCl -01- 0–28% 100 °C (212 °F) 0–18% –20 °C (–4 °F) -02- 0–18% 50 °C (122 °F) 22–39% –20 °C (–4 °F) -07- 22–39% 50 °C (122 °F) 0–13%...
  • Page 101: Sodium Chloride Solution -01- Nacl

    Concentration curves B.2 Sodium chloride solution -01- NaCl Refer to Figure 14 for the conductivity of sodium chloride solution at various concentrations and temperatures. Figure 14 The concentration of sodium chloride solution -01- NaCl (weight %) Note: Concentration measurement not possible in the gray shaded range.
  • Page 102: Hydrochloric Acid -02- Hcl

    Concentration curves B.3 Hydrochloric acid -02- HCl Refer to Figure 15 for the conductivity of hydrochloric acid (HCl) at various concentrations and temperatures.* Figure 15 The concentration of hydrochloric acid -02- and -07- HCl (weight %) Note: Concentration measurement not possible in the gray shaded range.
  • Page 103: Sodium Hydroxide Solution -03- Naoh

    Concentration curves B.4 Sodium hydroxide solution -03- NaOH Refer to Figure 16 for the conductivity of sodium hydroxide solution (NaOH) at various concentrations and temperatures. Figure 16 The concentration of sodium hydroxide solution -03- and -10- NaOH (weight %) Note: Concentration measurement not possible in the gray shaded range.
  • Page 104: Sulfuric Acid -04- Hso

    Concentration curves B.5 Sulfuric acid -04- H Refer to Figure 17 for the conductivity of sulfuric acid at various concentrations and temperatures.* Figure 17 The concentration of sulfuric acid -04-, -09- and -06- (weight %) Note: Concentration measurement not possible in the gray shaded range.
  • Page 105: Nitric Acid -05- Hno

    Concentration curves B.6 Nitric acid -05- HNO Refer to Figure 18 for the conductivity of nitric acid at various concentrations and temperatures.* Figure 18 The concentration of nitric acid -05- and -08- HNO (weight %) Note: Concentration measurement not possible in the gray shaded range.
  • Page 106 Concentration curves...
  • Page 107: Appendix C Passcode Editor

    Appendix C Passcode editor For applications requiring compliance to FDA 21 CFR Part 11, certain device functions must be protected with passcodes. Passcodes can be changed in the passcode editor. If passcode protection is not required, use the preset passcodes (Table 21).
  • Page 108 Passcode editor Table 21 Default passcode settings Display Function Default setting Press to accept the new ENTER Change administrator passcode YES SPCL ST passcode Press to exit the editor CONF 1 Not available for the Profibus PA and Foundation Fieldbus versions. Important Note: The passcode editor cannot be accessed without the administrator passcode.
  • Page 109: Appendix D Atex Safety Instructions

    The following ATEX safety instructions pertain to the electrodeless conductivity sensors, model 3700E-series, types 3708E2T, 3727E2T and 3728E2T manufactured by Hach Company. These sensors are described in the EC type-examination certificate TÜV 07 ATEX 553601 as part of the Transmitter si792x E.
  • Page 110 If it is still not possible to perform a clear assessment on safe usage, or applications areas other than those described are intended, then the application must be clarified with Hach Company/ Hach Lange GmbH. 5. A condition for the safe usage of sensors is compliance with the stated environmental conditions and temperature ranges.
  • Page 111 ATEX safety instructions plumbing standard) (refer to Figure 19). Mounting in the boundary wall between zone 0 and the less endangered area is to undertaken properly such that an adequately sealed gap (IP 67) is obtained. 8. The model 3700E sensors have been developed and manufactured in compliance with the applicable European directives and standards.
  • Page 112 ATEX safety instructions Figure 20 Sanitary-style sensor...
  • Page 113: Index

    Index 22 mA signal ..................39 4–20 mA output error notification ................. 39 assembly transmitter .................. 18 audit trail ..................... 14 calibration ................... 71 by product comparison ............... 74 methods ..................71 passcodes .................. 71 solutions ..................93 cleaning the transmitter ..............77 components ..................
  • Page 114 Index electrostatic discharge (ESD) ............. 20 error codes ..................80 FDA compliance ................. 14 hold mode during configuration ..............38 during output ................40 icons ....................33 setting on or off during hold ............42 measurement mode ................35 menu navigation ................. 38 navigation, menu ................
  • Page 115 Index Sensoface ..................79 solutions calibration ................... 93 symbols, display ................. 33 temperature compensation ..............41 temperature probe adjustment ............76 troubleshooting ................... 82 wiring 2-electrode probe ............24 4-electrode probe ..............26 diagram ..................22 HART communicator ..............29 sensor ..................25...
  • Page 116 Index...

This manual is also suitable for:

Si792 e series

Table of Contents