PAA-series (Cased A-Coil) Connection
Maximum piping length Maximum total piping with PAA connection depends on the number of PAA indoor
units connected. Please refer to the table below for the appropriate total maximum piping length the system
can be designed to.
Minimum piping length For branch box systems where PAA is the only unit(s) connected, the minimum
piping length to each PAA unit from the outdoor unit should be 33 ft.
Model
MXZ-SM36/48NAM
MXZ-
SM36/42/48NAMHZ
Specifications are subject to change without notice.
PAA-A18, 24, 30, 36, 42AA1/BA1/CA1
PAA-
PAA-
A18AA1
A24AA1
PAA-
PAA-
A18BA1
A24BA1
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Total
No PAA
Connected
Connected
Indoor
Capacity
(kBtu/h)
<27
492 ft
(150 m)
IDU
PAA-
PAA-
A30AA1
A36BA1
PAA-
PAA-
A30BA1
A36CA1
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Number of PAA units connected
1
492 ft
(150 m)
12
PAA-
Comment
A42BA1
PAA-
A42CA1
2
3 or more
(N/A,
(N/A,
*above 27
*above 27
kBtu/h)
kBtu/h)
© 2022 Mitsubishi Electric US, Inc.